Tao Yu, Per Kvols Heiselberg, Bo Lei, Chen Zhang, Michal Zbigniew Pomianowski, Rasmus Lund Jensen
Year:
2016
Languages: English | Pages: 11 pp
Bibliographic info:
Applied Energy, 169(May), 218–229

This paper investigates the dynamic cooling performance of a novel system combining natural ventilation with diffuse ceiling inlet and thermally activated building systems (TABS). This system is tested in the lab under three climatic conditions representing typical seasons in Denmark, including a typical winter day, a typical day in the transitional season and a typical summer day. The corresponding dynamic control strategies have been designed for these three cases in the measurements. In the winter case, TABS have to be activated for two hours to supply extra heating to ensure a comfortable indoor environment. In the case representing the transitional season, changing the ventilation rate during both occupied and un-occupied hours can ensure the thermal autonomy of the room without extra heating or cooling from TABS. In the summer case, the free cooling potential of ventilation air is limited due to the relatively high inlet air temperature. Therefore, TABS are activated for ten hours to supply the extra cooling. Due to the use of the diffuse ceiling, the whole-body and local thermal comfort conditions are quite good in the measurements. The dynamic measurements in the paper are beneficial to the future design and application of this system.