Zhou G, Melikov AK
Year:
2002
Bibliographic info:
Proceedings of Room Vent 2002 (8th International Conference on Air Distribution in Rooms) - 8-11 september 2002 - Moltke's palace, Copenhagen - Denmark - pp 357-360, 3 fig., 1 Tab., 8 ref.

This paper defines a new parameter : the equivalent frequency used for the description of the frequency characteristics of air velocity in turbulent flows.Analyses were performed to identify how much the accuracy of determination of the equivalent frequency depends on the characteristics of the velocity. Results of the analyses identified that the equivalent frequency of the velocity fluctuations in rooms is between 0.1 et 1 Hz, and 90 % of those records were between 0.2 and 0.6 Hz which is the frequency range identified to have most significant impact on people's draught sensation.