Burt T S
Year:
1998
Bibliographic info:
EPIC '98, Volume 1, pp 315-320

This investigation was carried out on a mechanically ventilated office building with a high prevalence of occupant symptoms. The commonest complaints were of dry air, stuffy air and noise. Occupant symptoms, however, were most strongly associated with reports of dusty air and static electricity. Allergic and asthmatic people suffered the most. Cleaning standards were high, and upgrading the air filters failed to give improvements in occupant symptoms. Air flows to the rooms were adequate, but air movements in the rooms were poor. Remedial measures should focus on improving air distribution, rather than increasing air flows.