Hartless R P, Llewellyn J W
Year:
1999
Bibliographic info:
20th AIVC and Indoor Air 99 Conference "Ventilation and indoor air quality in buildings", Edinburgh, Scotland, 9-13 August 1999

Temperature and relative humidity have been measured in a BRE test house to investigate the vapour content in the void beneath the timber floor. The void can be ventilated naturally or by means of a fan supplying or extracting air. The results show that air flow into and out of the void is stack dominated. The fan needs to supply or extract large volumes of air in order to disrupt this. Measurements and modelling have shown that the vapour content in the void is generally dependent on the level in external air, and that the contribution from the ground is usually small by comparison. The models are used to calculate rates of soil gas ingress.