AIVC - Air Infiltration and Ventilation Centre

Search form

EBC

You are here

Home  |  diffusion

Experimental study of indoor thermal environment for cold air distribution systems using various air outlets

Kashirajima Y, Sugiura T, Takahashi M, Sugihara Y, Ooshima N, 2002
air conditioning | air flow | cooling | diffusion
Bibliographic info: Preprint ASHRAE Transactions vol.108 no.2 2002 (USA) - paper presented at the ASHRAE Annual Meeting, Honolulu, June 2002 - 7 pp, 12 figs, 7 refs, 1 tab
Languages: English

Tests have been performed on several ceiling air diffusers supplied with low air temperatures (6 to 16°C - 90% humidity) to study water vapour condensation on diffusers surface. Results show that a supply air temperature of 11°C avoids most of condensatio