Duct leakage testing in Portugal, a consulting engineer view and experience

Carlos Pires Eurico Lisboa, 2018
Duct leakage testing
Bibliographic info: 39th AIVC Conference "Smart Ventilation for Buildings", Antibes Juan-Les-Pins, France, 18-19 September 2018
Languages: English Pages (count): 2

Duct leakage airflow in existing ductwork can reach values of over 20% of the design air handling unit (AHU) airflow, undermining efficiency and effectiveness of HVAC systems. We have measured, in an existing building where ductwork was installed 20 years before, with no special care on duct leakage and tight building construction schedules, operational duct leakage rates between 10% and 40% of the AHUs airflows. 


In an average office building, annual fan energy consumption is of the same magnitude of annual chiller energy consumption, minimising leakage has a significant impact on building energy consumption. 


Duct leakage testing gives knowledge of the magnitude of duct leakage airflow and, consequently, increasing awareness of the problem, will support the shift to installations with tighter ductwork. 


Related publications

Mandatory or voluntary building airtightness testing has come gradually into force in m
INIVE eeig, EU
This report summarizes the work of the initial working phase of IEA ECB Annex 62 Ventil
Maria Kolokotroni, Per Heiselberg, Lorenzo Pagliano, Jie Han, Regina Bokel, Peter Holzer, Annamaria Belleri, Denmark