Zhimin Du, Xinqiao Jin
Year:
2007
Bibliographic info:
Energy and buildings, Vol. 39, n° 8, August 2007, pp 923-934

Detection and diagnosis of multiple faults in VAV systems using principal component analysis (PCA) and joint angle analysis (JAA) are presented in that paper. With the multiple faults separated into different locations, joint angle analysis is used to isolate the faults one by one according to corresponding local models.