The climatical conditions in Sweden are such that it has almost always been necessary to tighten the houses quite thoroughly in order to avoid cold-draught and to make as good use of the heating as possible. Devices for intentional ventilation, such as ducts for the exhaust of "used" air, have been installed in Swedish houses for centuries. Thus the concept of infiltration and ventilation is not a new one. The more general introduction of central heating in the beginning of this century led to a relatively high degree of dependance on imported fuel.
The air change rate in existing, older blocks of flats having natural ventilation has been measured by the tracer gas method. Measurements were made in the buildings in as-found condition. The average air infiltration rate was 0.26 air changes/h (with the ventilation ducs closed), with an overall ventilation rate of 0.47 air changes/h. The average overall ventilation rate is very close to that recommended on the basis of health requirements, although values both above and below this are encountered in many flats.
A comparison of three injection manners, step-up, step-down and pulse, for determination of the mean age of air was made by using nitrous oxide and sulphur hexafluoride as tracer gases. The concentrations of nitrous oxide and sulfur hexafluoride were simultaneously measured with a dual-channel IR-analyzer. Tests were carried out in a test chamber with air change rates of 3 h-1 and 5 h-1. The tracer gases were injected under three conditions: into the inlet air and directly into the room with and without extra mixing fans.