Norwegian test methods for wind and rain penetration through windows

Part of an extensive research programme being carried out also in Denmark, Finland and Sweden. Describes 75 window tests and gives diagrams of air flow and rain penetration apparatus. Proposes tentative evaluation curves for air penetration of windows of a stringent kind suitable for a severe climate. For air pressure of 30-40 mm of water, an 'acceptable' air flow is about 30 m.m. per hour per test window, with 'good' at about 20 and 'excellent' about 11. The curves are shown graphically.

Air infiltration through revolving doors.

Describes experiments made to determine the air infiltration rate through revolving doors. Estimates infiltration by combining air leakage past the door seals with infiltration caused by the revolving of the door. Finds that air exchange depends on door speed and temperature differential and somewhat on wind and indoor air velocities. Gives flow past the door seals as function of indoor -outdoor pressure differential and flow related to door movement for a motor- driven revolving door and for a manually operated door for traffic rates up to 2000 people per hour.

Examination of the heat and air permeability of windows Untersuchung uber die Luft-und warme-durchlassigkeit von Fenstern

A study made to confirm the values given in german standard DIN 4701. considers theoretical natures of air permeability and the k-value as they concern windows. Finds that infiltration through windows without weather-stripping depends to such an extent on the quality of manufacture and fitting that essential differences between single-glazed, double-glazed and double windows scarcely exist. Finds no real difference between woodenand metal frames when new, but after normal wear and tear an average value of 3m(3)/h for each metre of gap at 1mm pressure difference is acceptable.

Air infiltration around windows Luftdurchlassigkeit von Fenstern.

Gives expression for the hourly air volume passing around a window due to pressure difference, and the total heat transference by infiltration. Describes tests made on site and in the laboratory on windows and discusses the resultant curves. The wood framed windows tested were either double-sashed or double- glazed units while the metal-framed windows were all double-glazed.

A proposed method of measuring the rate of air change in factories

Proposes a method for measuring the rate of air change in factories using ammonia as a tracer gas and measuring its rate of decay by a colorimetric method. The advantage is that extremely small quantities can be detected. The method is cheap, easy to use, reasonably accurate and unobjectionable to the occupants.

Retrofitting an existing wood-frame residence for energy conservation-an experimental study

Describes retrofitting a wood-frame residence, having only limited insulation in the attic, to reduce its energy requirements for heating and cooling. The three retrofit stages comprised : reducing air leaks ; adding storm windows : andinstalling insulation in the floor, ceiling and walls. The housewas extensively insulated to evaluate energy savings and other performance factors. an economic model was used to evaluate the cost effectiveness of the retrofit options.

Infiltration tests at Ringway House, Basingstoke

Describes the results of an investigation carried out to determine the rate of fresh air infiltration that is experienced during the winter in a modern air conditioned office building. Six different methods were employed to estimate the rate of infiltration through the building, four by direct measurement and two by calculation. The methods of direct measurement were,tracer gas decay, measured air flow through one floor, measured air flow through one air conditioning unit and measured change on power demand.

Wind pressures on multi-storey buildings.

Describes experiments in a wind tunnel on a model of a tall building of rectangular plan to show the effects of variation in wind velocity with height and the variation of local wind pressures with angle of wind. Discusses the effect of rounding the corners of the building.

Infiltration resistance to rain and wind of light metal facades Water-en winddichtheid van lichtmetalen gevels.

Reviews means of rain water penetration and how to apply one-stage weather proofing listing the disadvantages. Reviews research results obtained with two-stage weather proofing by adding an additional seal and summarises the pressure variations resulting from wind plus the design of horizontal and vertical joints between individual facade segments. Discusses the practical design of joint and sealant illustrating this for a few window types and adds that this design is also applicable for a complete curtain wall.

A method for the assessment of the wind induced natural ventilation forces acting on low rise building arrays.

Reviews existing methods for the prediction of infiltration rates and the factors influencing the pressure difference across buildings. Describes experimental procedure used in tests conducted in wind tunnel. Discusses results and presents prediction technique which enables surface pressures acting on aparticular building situated within an array of similar low rise buildings to be estimated, procedure takes account of the geometrical form of the building spacing parameters describing the array, direction of the wind and the upstream fetch conditions.