Building simulation on utilization of roof window in detached house by using cross-ventilation

The effects of roof window on ventilation flow rates and reduction of cooling loads in densely populated areas were investigated by using building simulations. In May of the intermediate season, when utilizing roof window, the cumulative number of air exchanges increased by 9 % to 12 % compared to that when the windows at side walls remained open only during the daytime. When the building coverage ratio increased from 0 % to 20 %, the cumulative number of air exchanges decreased and the cumulative cooling loads increased.

A Simulation Study on the Reduction of Cooling Loads in a Detached House by Cross-Ventilation using the Local Dynamic Similarity Model

A simulation study on the reduction of cooling loads by utilizing cross-ventilation was performed for a typically shaped house as defined by the Architectural Institute of Japan. A reduction in cooling load of around 50% could be achieved when the windows were opened liberally at night compared with the cooling load when all the windows remained closed, regardless of building coverage ratio.