Novel methods of inducing air flows within buildings.

Water use is distributed throughout building structures. Energy used to pump the water to higher levels in the building is not currently recovered, and is dissipated by performing work on air in the ventilation system which is vented to the atmosphere, when the water is discharged into the drainage stack. This energy can be utilised productively, however, by strategically placing the air inlet for the drainage stack inside the building, thereby utilising the potential energy stored in the water to draw air through the building.

The effects of building form on the natural ventilation of commercial buildings.

Wind pressures can significantly affect ventilation performance. However often they are overlooked in the design of a naturally ventilated building, with buoyancy forces presumed to offer the worst case scenario for design. The result is that airflow patterns and the ventilation performance of the building is often different from the design intent. Successful natural ventilation design requires careful consideration of the building form, and so must involve the architect at the early stages of fabric development.

A control system that prevents air from entering an air-handling unit through the exhaust air.

Traditional air-handling unit (AHU) control systems link the position of the exhaust air damper, recirculation air damper, and outdoor air damper. Tests at the National Institute of Standards and Technology (NIST) on a variable-air-volume (VAV) AHU have shown that air can enter the AHU through the exhaust air damper. This can negatively impact indoor air quality if the exhaust air duct is located near a pollution source. This paper presents a new control system for variable air volume AHU's that use volume matching to control the return fan.

Air dehumidification by absorption. (A model for numerical calculation)

Especially in modern buildings with small capacity of humidity storage it is necessary to reduce the humidity in the supply air. Normally this was done by using a refrigeration system mostly with CFC's. There are some alternative fluids available, but mostly they show a high global warming potential. All these systems need electrical energy to be driven and therefore it is necessary to consider other possibilities with alternative systems. The most promising systems are sorptive systems that are used now in open cycles.

The development of an occupancy-controlled exhaust air ventilation system.

Many dwellings with natural or gravity ventilation systems suffer from poor airchange rates. In Sweden, especially houses built in the 1960-ies and 1970-ies heated with electric resistance heating and thus without chimneys, are at risk. Improving the airchange rate in these houses is to some extent performed to decrease Radon gas concentrations where appropriate. For comfort, most homeowners learn to live with low airchange rates, accepting e.g. odours or window condensation and trying to compensate this with increased airing.

Evaluation of a controlled natural ventilation system.

The project described in this paper has performed simulations using a multi-zone air flow model (4(COMIS)) of three different passive stack ventilation systems. The objective of the simulation calculations was to evaluate system performances and to make suggestions for possible improvements of the systems.

A technique to improve the performance of displacement ventilation during cold climate conditions.

Ventilation by displacement is a type of ventilation where the air flow is thermally driven. By this arrangement one obtains two zones in the room - a lower zone with supply air conditions and an upper recirculation zone with extract air conditions. Cold climate causes downdraught from windows and external walls and results in a mixing of air from the upper into the lower zone. To avoid this problem during cold climate a new principle for ventilation by displacement is tested. Excess heat from the upper zone of the room is used for heating cold surfaces.

Evaluation of ventilation system in very low energy houses.

Since 1985 more than 170 very low energy houses, all of the same type and structure, were built in the Flemish Region, Belgium. Because conduction losses are very low, mean Urn-value 0.30-0.35 W/(m².K), ventilation losses become very important, up to 45% of the heat losses if no heat recovery is utilised. Three of the houses were monitored in detail for energy consumption, energy and ventilation efficiency. All houses are equipped with the same ventilation system: balanced mechanical ventilation with heat recovery.

The evolution of ventilation in manufactured housing in the Northwestern United States.

Electric utilities in the Pacific Northwest have spent over $100 million to support energy efficiency improvements in the HUD-code manufactured housing industry in the Pacific Northwest over the past several years. Over 65,000 manufactured housing units have been built since 1991 that exceed the new HUD standards for both thermal performance and mechanical ventilation that became effective in October, 1994. All of these units included mechanical ventilation systems that were designed to meet or exceed the requirements of ASHRAE Standard 62-1989.

The efficiency of single-sided and cross ventilation in office spaces.

This paper reports on work carried out at BRE to address the need for guidance on designing for natural ventilation via single-sided and cross-ventilation in office spaces and the limits of application in terms of plan depth. Present guidance suggests that natural ventilation will be adequate up to 6 m from the ventilating facade. This leads to the conventional design of offices up to 6 m deep on either side of a central corridor, giving as a rule of thumb a width of 15 m for a building with natural cross-ventilation.

Pages