Effects of groundwater flow direction on performance of ground heat exchanger borefield in geothermal heat pump systems using 3-D finite difference method

The effects of groundwater direction on performance of geothermal heat pump systems were analyzed using a 3-D finite difference method with rectangular meshes. Each borehole was approximated by a square column with the actual circular borehole section circumscribing the approximated square section. The fluid temperatures inside each borehole were calculated by discretizing borehole vertically into different segments.