From EN 779 to ISO 16890: a new worldwide reference test method for general ventilation filters

For testing of general ventilation filters, a completely new standard is now available and is going to replace EN 779 (2012) since the parts 1 to 4 of ISO 16890 (2017) have been adopted in August 2016 and published in 2017 at both international and European levels. With this new standard, the fractional efficiency of the new and the conditioned (24 hours to isopropanol vapour) filters is measured between 0.3 and 10 μm.

COMPARISON OF GENERAL VENTILATION AIR FILTER TEST STANDARDS BETWEEN AMERICA AND EUROPE

As the world trade field is expanding, international standard of air filter is urgently needed. At present,China is undergone its revising the national standards, therefore, the development of major air filterstandards between America and Europe is compared here. Diameter distribution of KCl aerosol used inASHRAE52.2 is similar with atmospheric dust, but research for test dust representing actual conditionis still needed. Concepts for electrostatic discharge between Europe and America are different, andclassification upon minimum life efficiency (MLE) is recommended.