Kato S., Yang J.H.
Year:
2004
Bibliographic info:
RoomVent 2004, 9th international conference in University of Coimbra - Portugal, 5-8th september 2004, pp 6, 7 Fig., 3 Tab., 7 Ref

A detailed study using Computational Fluid Dynamics (CFD) was conducted on the influenceof the difference in the effective diameters of air supply outlets (wind velocity, assuming the airflow rate to be constant) when using personal air conditioning with isothermal air currents. A method to analyze the new age of air (SVE3*) and the residual lifetime of air (SVE6*) was proposed and studied focusing on the individual supply openings and exhasut openings in a room with multiple supply openings and exhasut openings when using personal air conditioning. Personal air conditioning with the larger diameter opening resulted in less mixture with the surrounding air and a lower age of air than the smaller diameter, which therefore indicated better ventilation characteristics.