Deepak Sridhar, Kathleen Owen, Frank Mieseke, Ryan Shacklock, Colin van der Kuur
Year:
2026
Languages: English | Pages: 12 pp
Bibliographic info:
45th AIVC/ASHRAE IAQ- 13th TightVent - 11th venticool Conference - Montreal, Canada - 24-26 September 2025

Post-pandemic, the importance of indoor air quality (IAQ), particularly in mitigating infectious aerosols, has grown significantly. In Ontario, with 4,850 schools and approximately 280.6 million square feet of building space, schools have implemented strategies to reduce viral transmission and create safer environments for students and staff. Among the most common measures are ventilation and filtration, with MERV 13 and HEPA filters commonly suggested by school boards and policy makers. However, the installation of these filters in older schools presents challenges due to infrastructure limitations, potential overload of electrical systems, and increased operational costs. In this study, we present an innovative solution: silver-graphene oxide treated MERV-A 9-A (M9AZG) filters, treated with silver-graphene oxide, which offer superior protection against infectious aerosols while being compatible with existing HVAC systems. These filters have lower pressure drops (resistance to airflow) compared to most MERV 13 filters, resulting in significant energy savings. 
A pilot study at McKinnon Park Secondary School in Caledonia, Ontario, replaced existing MERV 13 (CM13) filters with M9AZG filters in two air handling units (AHUs), one providing ventilation to the gym and the other the cafeteria. The results showed that M9AZG filters achieved 22% energy savings due to lower pressure drops, reducing operational costs. In Infection Risk Management Mode (IRMM), due to M9AZG’s higher pathogen removal efficiency, thus requiring less outdoor air intake, the estimated energy savings in the gym were 5.86 kWh/ ft2 annually, equivalent to CAD 0.46/ft2, with a reduction of 0.75 kg/ft2 of CO2eq. In the cafeteria, the energy savings amounted to 18.11 kWh/ft2, or CAD 1.58/ft2, with a CO2eq reduction of 2.31 kg/ft2. These savings translate to 5.62 tonnes of CO2eq in the gym and 16.37 tonnes in the cafeteria annually. The extended filter life of M9AZG filters further reduces waste and resource consumption. This solution offers schools an efficient, cost-effective way to improve IAQ for infectious aerosols and energy efficiency without major infrastructure upgrades, contributing to healthier learning environments and long-term sustainability.