Tracer gas measurement in an office. Spangasmatuingar i ett rontovsrum.

Reports on research project to study the effects of different methods of heating an office, temperature and draught conditions, ventilation efficiency and heat storage in joint structures. Gives test room digramatically and tracer gas concentration under different conditions, both during summer andwinter.

Air tightness: Supermarkets and shopping malls.

Reports measurements of air leakage in several supermarkets and an enclosed shopping mall, all constructed between 1954 and 1979. All tests were conducted by using a large fan to depressurize the building. Gives graphs of leakage rates. Finds supermarkets are two to four times leakier than schools or high-rise office buildings.

Natural ventilation and the P.S.A. estate.

Gives results of a statistical survey of energy consumption in British government buildings. Suggests one reason for high consumption may be excessive ventilation. Reports field trial of the effect of reducing natural ventilation in a London office building. Window frames were sealed with a rubber mastic, giving an annual fuel saving of 22%. Finds measure was highly cost effective with a payback period of less than three years.< Discusses problem of heat loss through large doors in hangars and workshops.

Pages