AIVC Literature Lists
18: Control of Cross Contamination from Smokers
#NO 261 Ventilation : the human factors
AUTHOR Brundrett G.W.
BIBINF Proceedings of Aston University/Electricity Council Research Establishment
Conference on Controlled Ventilation ; held at University of Aston, 24 September
1975, 8p, 8 figs, 3 tabs, 21refs. #DATE 24:09:1975 in English.
ABSTRACT Gives state-of-the-art review of ventilation needed to control carbon
dioxide, odours, cigarette smoke and moisture mentioning main results. Gives
sketch graphs illustrating these results. Outlines the effect of opening
windows on air -change-rates andgives tables showing average window opening,
the moisture generation from various activities and the solar radiation falling
on vertical surfaces.
KEYWORDS ventilation needs, air quality. tobacco smoke,
#NO 502 Practical methods of reducing airborne contaminants in interior
spaces.
AUTHOR McNall P.E.
BIBINF Arch. Environ. Health. vol 30 p552-556. 5 figs 7 refs. #DATE 01:11:1975
in English #AIC 201
ABSTRACT Air contaminants include all gases, vapours, liquid droplets and
solids, including microogranisms of small size that can be dispersed in air
and that are unwanted. Contaminants can be removed by dilution of the air,
by deposition of particles on surfaces or by reaction with other materials
in air or in space (such as furnishings).< This article discusses in general
terms the reduction of contaminants and gives equations of concentrations
of contaminants after time t. Discusses types of filters and their effectiveness.
Reports field tests using tobacco smoke as the contaminant to test theoretical
results and finds excellent agreement. Outlines ways of controlling contaminants.
Concludes that it is difficult and expensive to control inside environmental
contaminants levels at values less than 20% to 25% of those occurring outside.
KEYWORDS air quality, pollution, tobacco smoke, particulate, filter
#NO 1147 Indoor air pollution -characterization, prediction and control.
AUTHOR Wadden R.A. Scheff P.A.
BIBINF A Wiley-Interscience Publication ISSN 0194-0287 1983 212pp. ISBN 0-471-87673-9
#DATE 01:01:1983 in English
ABSTRACT Explores the health implications, external and internal contributions,
and the measurement of indoor air pollution including such subjects as sampling
and analysis, calibration, time scale and interferences. Outlines the current
status of prediction techniques, including areas such as one-compartment
models, infiltration estimation, and empirical models. Summarizes the most
common control methods. Examines, in detail, the application of modelling
techniques to several typical indoor settings, for example, a restaurant,
kitchen or a conference room with smokers.
KEYWORDS air quality, pollution, modelling, prediction, measurement technique,
#NO 1455 Ventilation heat losses
Pertes de chaleur par renouvellement d'air
AUTHOR Hernot D., Porcher G.
BIBINF Chaud.Froid.Plomb. June 1984, vol.38, no.449, 65-72, 5 figs, 10 tabs.
#DATE 01:06:1984, in French,
ABSTRACT Describes the pollutant burdens on indoor air. Notes heat exchanges
by air renewal and associated heat losses. Examines how to determine the
required air change rate. Lists the minimum air changes for various types
of building with and without smoking. Treats air infiltration. Considers
how to reduce losses with air renewal by weather stripping, special air inlets,
reduction of the indoor air temperature, heat recovery with controlled mechanical
ventilation, heat pumps and heat pipes.
KEYWORDS ventilation, ventilation heat loss, air change rate, weatherstripping,
air inlets, heat recovery, mechanical ventilation
#NO 1465 Controlling indoor air pollution from tobacco smoke - models
and measurements
AUTHOR Offermann F J., Girman J R., Sextro R G.
BIBINF Indoor Air. Vol.1 Recent Advances in the Health Sciences and Technology
edited by B. Berglund, T. Lindvall and J. Sundell. Swedish Council for Building
Research. Stockholm. 20-24 August 1984, 257-264, 1 fig, 20 refs. in English
#DATE 20:08:1984 AIC bk,
ABSTRACT Examines the effects of smoking rate, ventilation, surface deposition,
and air cleaning on the indoor concentrations of respirable particulate matter
and carbon monoxide generated by cigarette smoke. A general mass balance
model is presented which has been extended to include the concept of ventilation
efficiency. Following a review of the source and removal terms associated
with respirable particulates and carbon monoxide, we compare model predictions
to various health guidelines.
KEYWORDS tobacco smoke, ventilation, carbon monoxide, pollutant, particulate,
modelling, ventilation efficiency, filter, air conditioning, health, air
quality
#NO 1475 Transport of radon from soil into residences
AUTHOR Nazaroff W W., Nero A V.
BIBINF Indoor Air, Vol.2, Radon, Passive Smoking, Particulates and Housing
Epidemiology edited by B.Berglund, T.Lindvall, J.Sundell. Swedish Council
for Building Research, Stockholm, 1984. 15-20, 1 fig, 1 tab, 24 refs. #DATE
00:00:1984 in English, AIC bk,
ABSTRACT To develop effective monitoring and control programs for indoor
radon it is important to understand the causes of the broad range of concentrations
that have been observed. Measurements of indoor radon concentration and air-exchange
rate in dwellings in several countries indicate that this variability arises
largely from differences among structures in the rate of radon entry. Recent
evidence further suggests that the major source of indoor radon in many circumstances
is the soil adjacent to the building foundation and that pressure-driven
flow, rather than molecular diffusion, is the dominant transport process
by which radon enters the buildings. Key factors affecting radon transport
from soil are radon production in soil, flow-inducing mechanisms, soil permeability,
and building substructure type.
KEYWORDS radon, house, measurement technique, air change rate, ventilation,
air flow, basement, pollutant, air quality, radioactive
#NO 1482 A prospective study of the health and comfort changes among
tenants after retrofitting of their flats
AUTHOR Iversen M., Bach E., Lundqvist G R.
BIBINF Indoor Air, Vol.2, Radon, Passive Smoking, Particulates and Housing
Epidemiology edited by B.Berglund, T.Lindvall, J.Sundell. Swedish Council
for Building Research, Stockholm, 1984. 237-241, 1 tab, 5 refs. #DATE 00:00:1984
in English AIC bk
ABSTRACT The prospective study included two groups, a study group, which
had retrofitting of their flats, and a control group not exposed to environmental
changes in their homes. The results clearly demonstrated a number of positive
effects of the replacement windows on health and comfort. This was related
to the thermal and acoustic environment. Effects normally considered to be
related to the indoor atmospheric environment showed positive changes as
well.This is contrary to the expected risk of uncontrolled reduced air infiltration
and ventilation rates. These findings are discussed with distinction between
acute and possible long term changes in air quality related to air tightening
and other energy conservation measures related to housing. The results of
this study also indicate that it would be desirable to conduct similar studies
under different climatic conditions and for other types of buildings, but
with the same methodology so that the studies would be comparable.
KEYWORDS retrofitting, house, flat, energy conservation, comfort, thermal
comfort, air infiltration, ventilation, air change rate, air quality, air
tightness, window, double glazing, health
#NO 1544 Air infiltration. Where we stand today. Outlook.
Zusammenfassung. Wo stehen wir heute. Ausblick.
AUTHOR Wyssling U.
BIBINF Heizung und Luftung/Chauffage et ventilation, 1984, No 5, p34-36.
#DATE 00:00:1984 in German
ABSTRACT Briefly notes the significance of ventilation heat losses for energy
consumption. Notes the main sources of air pollutants in indoor air and the
recommended fresh air rates per person for housing, for smokers and non-smokers.
Notes the need for a well-sealed facade with mechanical ventilation and for
judicious facade leakiness in the absence of mechanical ventilation. Notes
the long-term need is for improved control of air infiltration. Notes briefly
the AIC publication "Air infiltration control in housing". Treats
the significance of ventilation heat losses for sizing heating installations.
Notes methods of checking air leakiness of buildings. Concludes by noting
research results accumulated over the last few years in this field. Notes
possibilities for cooperation between interested parties for control of air
infiltration.
KEYWORDS air infiltration, energy consumption, ventilation needs, natural
ventilation, mechanical ventilation, heating
#NO 1734 Indoor air quality environmental information handbook: combustion
sources.
AUTHOR Mueller Associates, Syscon Corporation, Brookhaven National Laboratory.
BIBINF Washington:US Dept of Energy,January 1985. 206pp. 63 figs, 54 tabs,
201 refs. #DATE 00:01:1985 in English AIVC bk
ABSTRACT This environmental information handbook was prepared to assist both
the non-technical reader and technical persons, such as researchers, policy
analysts, and builders/designers, understand the current state of knowledge
regarding combustion sources of indoor air pollution. Quantitative anddescriptive
data addressing the emissions, indoor concentrations, factors influencing
indoor concentrations, and health effects of combustion-generated pollutants
are provided. In addition, a review of models, controls, and standards applicable
to indoor air pollution combustion sources is presented. The emphasis is
on the residential environment. The data presented has been compiled from
government and privately-funded research results,conference proceedings,
technical journals, and recent publications. It is intended to provide the
technical reader with a comprehensive overview and reference source on the
major indoor air quality aspects relating to indoor combustion activities,
including tobacco smoking. In addition, analysis has been performed to estimate
potential concentration levels in residential settings. This information
can be used by homeowners to evaluate the trade-offs involved in potential
mitigating measures and to make better decisions regarding combustion sources
of indoor pollution within their homes.
KEYWORDS air quality, health, nitrogen oxides, carbon monoxide, particulate,
tobacco smoke, pollutant, standard, empirical models, measurement technique,
mathematical modelling
#NO 1825 Indoor air pollution.
AUTHOR Repace J L
BIBINF Environment International, 1982, Vol 8, p21-36. 9 figs, 2 tabs, 97
refs. #DATE 00:00:1982 in English
ABSTRACT Discusses the nature of the problem of indoor air pollution, limitations
in the authority of established health agencies in the US to control the
problem, research needs and some control options. Indoor pollutants of current
concern include radon, tobacco smoke, emissions from unvented indoor combustion
appliances, aeropathogens, formaldehyde and pesticides.
KEYWORDS air quality, pollutant, radon, tobacco smoke, formaldehyde, organic
compound
#NO 1827 Air quality control: measurements and experiences.
Regelung der luftqualitat.
AUTHOR Geerts J
BIBINF HLH, 1985, Vol 36, No 7, p354-358. 6 figs, 8 refs. #DATE 00:07:1985
in German Refrigeration, Air Conditioning and Heat Recovery, September 1985,
p34,38,40,43,44,50 in English
ABSTRACT Presents a control system for mechanical ventilation of large rooms
such as meeting rooms, cinemas, department stores, etc, based on air quality.
Gas sensors are used to measure the pollutant levels and regulate the air
flow in the room in relation to the number of people, level of tobacco smoke
and other pollutants. The CO2 levels are also recorded. The resulting energy
saved is given for three Norwegian buildings.
KEYWORDS controlled ventilation, air quality, commercial building
#NO 1829 Ventilation requirements in occupied spaces during smoking
and nonsmoking occupancy.
AUTHOR Cain W S, Leaderer B P
BIBINF Environment International, 1982, Vol 8, p505-514. 16 figs, 13 refs.
#DATE 00:00:1982 in English
ABSTRACT This investigation looks at sensory (odour, irritation) and physical
criteria for ventilation requirements, paying particular attention to the
difference between smoking and nonsmoking occupancy in a well-controlled
environmental chamber. More than 200 persons (visitors) made judgements of
odour intensity and acceptability under various conditions of occupancy (up
to 12 nonsmoking occupants, a temperature of up to 25.5 degrees C, up to
16 cigarettes smoked per hour). The results implied that under nonsmoking
conditions and moderate humidity only about 7.5 cfm (3.8 L sec-1) of fresh
air per occupant sufficed to satisfy visitors, but that under smoking conditions
at least 5 times as much fresh air is necessary. The estimate of ventilation
requirements for smoking was derived in part from measurements of carbon
monoxide and total suspended particulate (TSP) mass concentration. Levels
of TSP achieved during realistic smoking and ventilation rates exceeded levels
deemed acceptable outdoors. Surfaces in the chamber played an important role
in the elimination of particles, presumably via adsorption. Use of an electrostatic
precipitator could keep TSP levels under control. Nevertheless, it remains
to be seen whether control of TSP will eliminate the need for enormous ventilation
for odour control during smoking occupancy.
KEYWORDS ventilation needs, odour, tobacco smoke, carbon monoxide, particulate
#NO 1832 Relation between indoor air formaldehyde concentrations and
ventilation rates for a group of sixteen new houses.
AUTHOR Figley D A
BIBINF Presented at the 78th Annual Meeting, Air Pollution Control Association,
Detroit, USA, June 16-21, 1985. 14p. 4 figs, 1 tab, 10 refs. #DATE 00:06:1985
in English
ABSTRACT This study examines the experimental determination of the apparent
net formaldehyde source strength in a group of sixteen nominally identical
wood frame houses built by one contractor using similar construction details
and materials. The houses were very well sealed, with a mean induced air
leakage rate of 0.23 ach at 50 Pa, with a standard deviation of 0.09 ach.
All of the houses had air-to-air heat exchangers, which were operated at
various flow rates. The seven day average formaldehyde levels were measured
and were correlated to ventilation rates (using simple steady-state models)
to determine the apparent formaldehyde source strengths. The houses were
divided into three groups: unoccupied (4 houses), occupied non-smoking (10),
andoccupied smoking (2). Two of the nine occupied houses had formaldehyde
levels above the maximum level suggested by ASHRAE. They also had heat exchangers
operating only one third of the time.
KEYWORDS bungalow, formaldehyde, air tightness
#NO 1839 Indoor by product levels of tobacco smoke: a critical review
of the literature.
AUTHOR Sterling T D, Dimich H, Kobayashi D
BIBINF Journal of the Air Pollution Control Association, March 1982, Vol
32, No 3, p250-259. 8 tabs, 66 refs. #DATE 28:12:1981 in English
ABSTRACT The levels reported in diverse publications of by products of cigarette
combustion (acrolein, aldehydes, aromatic hydrocarbons, carbon monoxide,
nicotine, nitrogen oxides, nitrosamines, particulates, and others for which
scattered information is available - HCN, ketones, nitriles) are summarized
in tabular form. Summaries also include information on test conditions such
as ventilation, size and types of premises, monitoring conditions, number
of smokers, and rate of smoking. Current methodology emerging from a review
of a wide variety of measuring practices is critically evaluated and discussed.
Major findings are reviewed. In conclusion, the presently available data
are useful for gaining a reasonably accurate perspective of the amount of
combustion products contributed by cigarette smoking under different conditions,
even though serious methodological problems persist.
KEYWORDS tobacco smoke, review, ventilation
#NO 1842 Comparison of non-smokers' and smokers' perceptions of environmental
conditions and health and comfort symptoms in office environments with
and without smoking.
AUTHOR Sterling T D, Sterling E M
BIBINF Ergonomics and Health in Modern Offices/Edited by E Grandjean. London:Taylor
and Francis,1984. p34-40. 6 tabs, 11 refs. #DATE 00:00:1984 in English
ABSTRACT 1100 branch members of the New York branch of the Office and Professional
Employees International Union working in nine office buildings filled out
a detailed questionnaire on working conditions and health comfort complaints.
Data were classified according to smoking habits of respondents and office
rules regulating smoking. Neither smokers nor non-smokers differed in prevalence
of complaints for a large variety of symptoms caused by smoking conditions
in the office but more non-smokers complained about stressful conditions
in offices where smoking was restricted or prohibited than where smoking
was permitted. Lack of differences in comfort complaints between smoking
and non-smoking offices does not contradict findings of irritated responses
due to passive exposure to smoke in controlled, especially chamber studies.
Responses of the OPEIU members were taken under normal conditions of ventilation
and lighting and no specific attention was drawn to the presence or absence
of smokers. The findings are also in agreement with a study conducted by
the US National Institute for Occupational Safety and Health where no association
was found between density of smokers and levels of complaints.
KEYWORDS tobacco smoke, air quality, human comfort
#NO 1860 Indoor air quality and human health.
AUTHOR Turiel I
BIBINF Stanford,USA:Stanford University Press,1985. 173p. figs, tabs, refs.
#DATE 00:00:1985 in English AIVC bk
ABSTRACT Provides general information on indoor air pollution sources, the
pollutants commonly found indoors and their potential health effects. Contains
chapters on formaldehyde and other household contaminants, radon, particulates,
combustion products, smoking, energy-efficient buildings, control of indoor
air pollutants, air quality in office buildings, and legal and regulatory
issues in the USA. Further sources of information are given.
KEYWORDS air quality, formaldehyde, radon, particulate, tobacco smoke, smoke,
office, residential building
#NO 1935 Indoor air quality, infiltration and ventilation in residential
buildings. Final report.
AUTHOR Nitschke I A, Traynor G W, Wadach J B, et al.
BIBINF Prepared by W S Fleming and Associates, Inc, for New York State Energy
Research and Development Authority and Niagara Mohawk Power Corporation.
NYSERDA Report 85-10. March 1985. 236p. figs, tabs, refs. #DATE 00:03:1985
inEnglish
ABSTRACT Sixty houses built with widely different construction practices
and located in different areas in upstate New York were monitored for airtightness
(using fan pressurization) and integrated radon concentrations in indoor
air, household water, and soil surrounding the house basement. Thirty of
the houses were also monitored for air exchange rates (using perfluorocarbon
tracer gas), combustion pollution (nitrogen dioxide, carbon monoxide, and
respirable suspended particulates), and formaldehyde for a total of forty-one
one week periods using integrating samplers. Most of the thirty houses had
suspected combustion-related indoor pollution sources. Using extensive real-time
instrumentation, detailed follow-up monitoring in houses with high levels
of indoor pollution was performed to determine the reasons for the high pollution
levels and to evaluate temporary control techniques to reduce indoor levels
below air quality guidelines. The long-term effectiveness of these techniques
was then tested using the same integrating samplers of the original surveys.
Overall results of this monitoring indicated that unvented kerosene heaters
were responsible for high indoor nitrogen dioxide levels: smokers and some
wood stoves and fireplaces were sources of indoor respirable suspended particulates:
automobile exhaust in an attached garage was the cause of high indoor carbon
monoxide levels in one of the houses: new panelling and high humidity levels
were associated with high formaldehyde levels in one of the houses: houses
built on upstate New York black shales were more likely to have high radon
levels and houses with vented crawl spaces were less likely to have high
radon levels. The most effective general control technique was the identification
of the sources of pollution and the removal and/or the isolation of the sources
from the indoor environment. If the sources could not be avoided, their effects
could be reduced by local ventilation at the source, and/or filtration, and/or
increased whole-house ventilation if the pollution source strength was relatively
low and diffuse.
KEYWORDS air change rate, air tightness, radon, nitrogen dioxide, carbon
monoxide, particulate, formaldehyde
#NO 1949 Regulatory aspects of indoor air quality - a UK view.
AUTHOR Llewellyn J W, Warren P R
BIBINF Proceedings of the Air Pollution Control Association International
Specialty Conference on Indoor Air Quality in Cold Climates: Hazards and
Abatement Measures, 29 April - 1 May, 1985, Ottawa. 10p. 21 refs. #DATE 00:00:1985
inEnglish
ABSTRACT Specific indoor air quality issues that have arisen in the UK in
recent years have involved asbestos, formaldehyde, pesticide residues, radon
and combustion products. Different measures have been taken with regard to
each of these substances. In general, an education approach has been adopted,
although national standards, industry self-regulation and some regulatory
measures have been used. In the UK, control of ill defined, distributed or
non stationary indoor air pollutants such as body odour, tobacco smoke and
water vapour, is considered to be best achieved by suitable ventilation.
Research is being undertaken on methods of measurement of natural ventilation
rates of buildings using automated multiple tracer gas techniques. Computer
based models for predicting natural ventilation and infiltration rates are
being developed.
KEYWORDS air quality, formaldehyde, radon, carbon monoxide, building code,
standard
#NO 2108 Control of the outdoor air intake by the use of contaminant
monitoring.
AUTHOR Suomi U
BIBINF Proceedings of the CLIMA 2000 World Congress on Heating, Ventilating
and Air-Conditioning, Copenhagen, 25-30 August 1985. Edited by P O Fanger.
Vol 4. Indoor Climate. p321-325. 2 figs, 3 refs. #DATE 00:08:1985 in English
ABSTRACT Reviews the possible indicators for monitoring the indoor air quality
and controlling the outdoor air intake. The technical feasibility of the
system is also discussed. At present CO2 seems to be the best and most reliable
indicator for indoor air quality when occupancy load varies. In future, however,
it is likely that measuring devices based on semiconductor technology and
measuring devices for particles will be more reliable and inexpensive and
so very suitable for controlling the air quality, because they can take into
account both occupancy load and tobacco smoke. The air quality controlled
ventilation system is easy to connect in almost all air conditioning systems,especially
if recirculated air is used. In most buildings measuring from one point (exhaust
air) will give an adequate result for controlling the air conditioning system.
KEYWORDS controlled ventilation, carbon dioxide, particulate, air quality
#NO 2160 Pollution begins at home.
AUTHOR Matthews R,
BIBINF New Scientist, 5 December 1985, Vol 108, No 1485, p34-37, 6 figs,
1 tab. #DATE 05:12:1985 in English
ABSTRACT Points out that increased thermal insulation and draughtproofing
of homes can increase the risk to health of indoor air pollution. Includes
condensation as a pollutant along with associated mould growth. Notes collaboration
by Pilkington the glass company and the Timber Research and Development Association
plus Laing the housebuilding group, to combat condensation by passive ventilation.
Treats sources of indoor air pollution - formaldehyde, asbestos, gas appliances,
tobacco smoke, thoron, radon. In some homes in the UK the radon level is
so high that occupants face a significant risk of contracting lung cancer.
Treats research into ways of reducing level of radon and other pollutants
in homes. Recommends the controlled introduction of adequate amounts of fresh
air. Notes the dangers of indoor air pollution in offices - the sick building
syndrome.
KEYWORDS air quality, pollution, condensation, formaldehyde, gas, tobacco
smoke, radon
#NO 2229 Air quality control - measurements and experiences.
AUTHOR Geerts J
BIBINF Heat Vent Engr, Vol 59, No 678, p18-22. 6 figs, 2 tabs, 8 refs. #DATE
00:09:1986 in English
ABSTRACT Too high a concentration of certain gases (e.g. water vapour, carbon
dioxide, tobacco smoke, alcohol, etc.) in public buildings can damage the
health. Even low concentrations can cause discomfort and make the room air
seem unpleasant. This paper describes this subjective perception of air qulaity.
It is shown that installation of an appropriate sensor can make substantial
energy savings.
KEYWORDS water vapour, carbon dioxide, tobacco smoke, public building, health,
air quality
#NO 2275 The feasibility of using a photoelectric cigarette smoke
detector for energy efficient air quality control.
AUTHOR Nelson R M, Alevantis L E
BIBINF ASHRAE Trans, 1985, Vol 91 Part 2A, No 2891, p75-84. 7 figs, 1 tab,
10 refs. #DATE 00:00:1985 in English
ABSTRACT The object of this study was to determine the feasibility of using
a smoke sensor to monitor and control cigarette smoke levels in occupied
spaces and also to determine whether the use of such a detector could result
in energy savings. A smoke detector was built and tested. The experimental
results show that the smoke sensor output is a function of cigarette smoke
concentration and that the smoke sensor gives a rapid and continuous response.
In addition, a computer program that simulates the transient mass and energy
interactions in buildings was modified so that the impact of ventilation
strategies on indoor air quality and energy for an arbitrary test case show
that the use of a smoke sensor to detect cigarette smoke particulates and
to control ventilation can allow indoor air quality to be continuously maintained
at acceptable levels while minimizing energy consumption.
KEYWORDS tobacco smoke, smoke sensor, numerical modelling
#NO 2350 Causes, effects, and relief from formaldehyde build-up in
the home.
AUTHOR Meyer C B
BIBINF In "Indoor air quality and conservation", proceedings, Bellevue,
Washington, November 15-16, 1984, edited by Chuck Eberdt, Seattle, Energy
Business Association, August 1985, p49-60, 5 figs.
#DATE 00:08:1985 in English AIVC bk
ABSTRACT Discusses sources of formaldehyde indoors, e.g. smoking, formaldehyde
resins, and release of formaldehyde from chipboards and foam insulation,
and the importance of ventilation in removing excess pollutants. Factors
influencing the amount of formaldehyde release include age of materials,
temperature, moisture variations, ventilation. Emphasises the importance
of quality control, standards and tests such as FTM-1 and FTM-2.
KEYWORDS formaldehyde, mobile home, tobacco smoke, pollutant
#NO 2429 Discussion on indoor air quality.
Diskussion um die Raumluftqualitat.
AUTHOR Rosenkranz
BIBINF TAB, No 11, 1986, p759-762, 13 tabs, 15 refs. #DATE 00:11:1986 in
German
ABSTRACT Discusses sources of indoor air pollution; carbon dioxide and moisture
from occupants and chemicals from building materials and combustion processes,
wood, preservatives, and tobacco smoke, as well as pollutants coming from
outdoor air and means of controlling those pollutants. Presents useful tables
of chemical pollutants and concentrations.
KEYWORDS formaldehyde, pollutant, asbestos, pentachlorphenol, combustion,,
combustion product, tobacco smoke, radon
#NO 2552 Causes, consequences, and control of indoor air pollution
: a selected bibliography, 1980-1985.
AUTHOR Koshy P J
BIBINF Vance Bibliographies, Monticello, Illinois 61856, Architecture Series:
bibliography, July 1986, 31p. #DATE 00:07:1986 in English
ABSTRACT This bibliography is an effort to bring together a selected list
of literature on the subject of indoor air pollution produced from 1980 to
1985, and is aimed at the research worker as well as others interested in
the subject.
KEYWORDS indoor air, pollution, asbestos, building material, radon, radon
daughters, formaldehyde, combustion heating, tobacco smoke
#NO 2564 An investigation into cigarette smoke in different types
of room.
AUTHOR Narasaki M
BIBINF Reprint from : 6th International symposium on contamination control,
1982, p263-266, 9 tabs. #DATE 00:00:1982 in English
ABSTRACT The degree of indoor pollution depends, together with other factors,
on the amount of tobacco smoked and upon the ventilation rate supplied. We
therefore need to quantify the pollution generated by cigarette smoking so
that it can be diluted to an acceptable level. The quantity of cigarettes
smoked will depend upon the use of the room. We therefore need to identify
the smoking habits of the occupants of different types of room. This paper
describes the investigation by Osaka University to quantify the proportion
of occupants who smoke, the quantity of cigarettes smoked, the time taken
to smoke a cigarette and the interval between cigarettes smoked. The spaces
studied were in office, a conference room, a cafe and the waiting room in
a bank.
KEYWORDS tobacco smoke, pollution, ventilation rate, occupant behaviour,
indoor climate
#NO 2572 Indoor air pollution in office buildings with oxides of nitrogen.
AUTHOR Yoshizawa S
BIBINF Reprint from : 6th International symposium on contamination control,
1982, p225-260, 3 figs, 7 tabs, 2 refs. #DATE 00:00:1982 in English
ABSTRACT To clarify the mechanism and the level of nitrogen oxides of indoor
and outdoor origin in air conditioned buildings, field measurements were
made in several buildings including one small building, three intermediate,
two subway stations. The spatial distribution of NO, NO2, CO, CO2 in rooms
was obtained and the cumulative frequency distribution curves were examined.
The magnitude of spatial variation was expressed in coefficient of variation
and the values were not much different from those of CO2. The mass balance
of oxides of nitrogen was calculated and compared with those calculated from
actual smoking amount. The relation of the concentration just outside the
building and thoseof air pollution control station, indoor, outdoor concentration
were examined by testing the correlations and ratio, also correlation of
values at two measurement stations in a same building were examined and NO
showed very strong correlations. The correlation of number of occupants and
the concentration of NO, NO2, CO, CO2 were calculated and there were little
correlation except with CO2.
KEYWORDS indoor climate, pollution, office building, nitrogen oxides
#NO 2912 Impact of a new smoking policy on office air quality.
AUTHOR Lee H K, et al
BIBINF in: Indoor air quality in cold climates: hazards and abatement measures.
APCA Specialty Conference 1986, p 307-322, 6 figs, 7 tabs, 8 refs. #DATE
00:00:1986 in English
ABSTRACT A new smoking policy was implemented on a trial basis on one floor
of a large modern Canadian office building. Smoking was limited to a single
enclosed room which shared the same recirculating-type ventilation system
with the rest of the floor. Environmental monitoring was conducted on the
test floor and a control floor during three consecutive working days both
before and after policy implementation. Hourly levels of respirable suspended
particulate (RSP), carbon monoxide (CO) and carbon dioxide (CO2) were monitored
on thefloors and in the designated smoking area throughout the workday. Temperature
and relative humidity were monitored at specific sites on each floor and
the quantity of outdoor air supplied to each floor was measured on a daily
basis. A voluntary questionnaire was circulated to all staff to detect any
changes in personal smoking habits over the course of the study. Results
of the investigation showed statistically significant reductions of RSP and
CO concentrations on the test floor. After standardization to the control
floor, the test floor results indicated a reduction of RSP and CO, 23% and
7.2%, respectively.
KEYWORDS tobacco smoke, office building, mechanical ventilation, particulate,
carbon monoxide, carbon dioxide, questionnaire
#NO 3072 Indoor air quality; acceptable standards and building design.
AUTHOR NSCA
BIBINF UK, National Society for Clean Air, 1987 Workshop Proceedings. #DATE
00:00:1987 in English
ABSTRACT Contains 12 papers concerning indoor air quality as follows:1.Changes
in building design, use and ventilation by D P Gregory; 2. The influence
of energy conservation measures by A Warren; 3. Hazardous building materials
and their problems by C Marsh; 4. Passive smoking by M.Squirrell; 5. Pollution
from airborne metals by R Harrison; 6. Perception of and reaction to noise
by I Flindell; 7. Exposure to pechloroethylene in residents living above
dry cleaning establishments by T C Aw; 8. Chemical sensitivity in patients
referred to the department of allergy and environmental medicine at the Lister
Hospital by J Monro; 9. Controlling air quality in car parks by M F Fox;
10.Air infiltration techniques by P C MacDonald; 11. Thoughts on avoiding
trouble by R A Waller and 12. Conclusions and policy and practice guidelines.
Includes also discussion session.
KEYWORDS indoor air quality, pollutant
#NO 3148 Market analysis of sensors for the use in demand controlled
ventilating systems.
AUTHOR Raatschen W
BIBINF in: "Effective Ventilation", 9th AIVC Conference, Gent,
Belgium, 12-15 September, 1988. #DATE 00:09:1988 in English
ABSTRACT In the framework of a project of the International Energy Agency
(IEA), IEA-Annex XVIII - Demand Controlled Ventilating (DCV) Systems, which
started in Fall 1987, a review of the state of the art of already existing
DCV systems and devices has been undertaken by all participating countries.
This paper is concerned with air quality sensors which may be suitable to
control air quality on demand. The dominant contaminants are not only varying
in different kinds of buildings (dwellings, schools, stores etc.) but also
from room to room due to different ways of utilizing the spaces. Climatic
and environmental differences will have a further impact on the DCV system.
In this context contaminants are discussed which have a dominant regime and
impact on indoor air quality and which cannot be avoided by controlling the
source. These are humidity, odours (indicator e.g. carbon dioxide CO2), fumes,
and tobacco smoke. The working principles of various sensors are outlined
and possibilities of application discussed.
KEYWORDS market study, demand-controlled ventilation, ventilation system,
indoor air quality, pollutant, humidity, odour, tobacco smoke
#NO 3495 Fresh air for sedentary occupants.
AUTHOR Appleby P
BIBINF Building Services, July 1989, pp.55-56, 1 tab, 2 figs, 7 refs. #DATE
00:00:1989 in English
ABSTRACT Paul Appleby examines the basis of ventilation requirements and
recommendations for buildings and compares the imminent ASHRAE Standard with
the latest thinking in Scandinavia. He defines fresh air, and discusses odour
control, tobacco smoke, intermittent and transitory occupancy, and finally
draws his own conclusions.
KEYWORDS tobacco smoke, buildings, odour, ventilation
#NO 4032 Use of air cleaners to reduce outdoor air requirements.
AUTHOR Meckler M, Janssen J E
BIBINF in: Engineering solutions to indoor air problems, proceedings IAQ
88, ASHRAE 1988, pp130-147, 6 figs, 3 tabs, refs. #DATE 00: 00:1988 in English
ABSTRACT The proposed revision to ASHRAE Standard 62-1981, "Ventilation
for Acceptable Indoor Air Quality", recommends a minimum of 15 cfm of
outdoor air per person. This amount is needed to control occupant odours
and guarantee that the concentration of carbon dioxide will not exceed 1000
ppm. Additionally, other recognised contaminants, including formaldehyde,
office products, building materials, and tobacco smoke, will be maintained
at acceptable levels. Most applications (i.e. offices) where the above contaminants
can be expected to be found generally require more outdoor air. Air-cleaning
systems that effectively remove the major contaminants can reduce the amount
of outdoor air required. However, this generally requires an increase in
the amount of recirculated air. A model is developed and equations are presented
for calculating the amount of outdoor air required, space concentration of
filtered contaminants, or the amount of recirculation needed. These parameters
are dependent on the type of air distribution system (VAV or constant volume),
supply temperature (constant or variable), and the use of outdoor air (constant
or proportional). Also required are the air cleaner efficiency, ventilation
efficiency, recirculation factor, and the flow reduction factor (with VAV
systems). Sufficient design of air cleaning systems can reduce the amountof
outdoor air required.
KEYWORDS outdoor air, air cleaning, model
#NO 4038 Health effects of heating with wood: chest illness in young
children and indoor heating with woodburning stoves.
AUTHOR Osborne J S
BIBINF in: The human equation: health and comfort proceedings IAQ 89, pp17-22,
1 fig, 2 tabs, refs. #DATE 00:00:1989 in English
ABSTRACT This study investigated a suspected relationship between the occurrence
of chest illness in young children and use of woodburning stoves (WBS) for
indoor heating. Data were prospectively collected during the winters of 1980,
1981 and1982 for 62 mid-Michigan children age one to seven years (31 randomly
selected children from WBS-heated homes and 31 controls from homes heated
by conventional sources matched for age, sex, and place of residence). The
specific a priori research hypotheses were that the proportion of children
having a chest illness would be significantly greater in the WBS group than
in the control group, that a greater proportion of WBS groupchildren would
have chest illnesses lasting at least one week, and that a greater proportion
of WBS group children would be hospitalised before age two years for chest
illness. Results showed a significant difference between the WBS and control
groups in the proportion of children having a chest illness from 1980-1982
(especially bronchitis, upper respiratory infection, and pneumonia); 39%
of the WBS group and 19% of controls had at least one such illness. Further,
the WBS group has a greater proportion of chest illnesses lasting at least
one week (32% vs.16%) and a greater proportion of hospitalizations for chest
illness before age two years (16% vs. 10%). These differences were not accounted
for by medical histories, frequency of physician visits, sociodemographic
factors, or exposure to other sources of indoor air pollution investigated
in the study (i.e. parental smoking, cooking with gas, urea-formaldehyde
foam insulation) and suggest that indoor heating with WBS may be a significant
risk factor for chest illness in young children.
KEYWORDS health, combustion product
#NO 4365 Smoking out the standards.
AUTHOR Pyatt J
BIBINF UK, Building, 23 February 1990, pp27-28 (Doors and windows supplement).
#DATE 23:02:1990 in English
ABSTRACT Discusses the case for a British Standard on smoke controls.
KEYWORDS smoke, air movement, fire
#NO 4410 On the management of the indoor radon problem in Belgium.
AUTHOR Poffijn A, Uyttenhove J, Vanmarcke H
BIBINF Canada, Indoor Air '90, Proceedings of the 5th International Conference
on Indoor Air Quality and Climate, Toronto, 29 July -3 August 1990, Volume
1 "Human Health, Comfort and Performance", pp 387-392. #DATE 00:07:1990
in English
ABSTRACT The reference value of 63 Bqm-3 for radon in Belgium is comparable
to the results obtained in neighbouring countries. There exists a significant
distinction between the north of the country (average 48 Bqm-3) and the south
(average 85 Bqm-3), where much higher concentrations are regularly found.
This can be explained mainly by differences in the geology of the underlying
soil. The very high concentrations of the order of thousands of Bqm-3 found
on some occasions raise the problem of remediation. In collaboration with
the inhabitants and the local authorities the effect of different techniques
are actually being tested and the results will be followed-up. The risk assessment
based uponuranium miner studies leads to an estimation of the etiological
fraction for radon of the order of 10 to 30%. As the extrapolation technique
for low doses is a matter of controversy, an epidemiological study of the
case-control type was set-up by the end of 1987. The preliminary results
of this pilot study, indicate a significant increase in risk for the group
of the exposed (greater than 100 Bqm-3) current smokers and non smokers compared
to the corresponding non-exposed reference groups (odds ratio resp. 5.2 and
8.6) while for ex-smokers no effect was observed.
KEYWORDS radon, residential building
#NO 4750 Ventilation requirements in buildings: control of occupancy
odour and tobacco smoke odour.
AUTHOR Cain W S, et al
BIBINF Atmospheric Environment, Vol 17, No 6, 1983, pp 1183-1197, 13 figs,
2 tabs, refs. #DATE 00:00:1983 in English
ABSTRACT Psychophysical measurements of odor, supplemented with certain physical
measurements, were taken to examine ventilation requirements during smoking
and nonsmoking occupancy in an environmental chamber. The facility provided
the means to compare impressions of visitors (persons who inhaled air from
the chamber only briefly) with impressions of occupants. For nonsmoking occupancy,
47 combinations of temperature, humidity, ventilation rate and occupancy
density were examined. Odor level depended entirely on ventilation rate per
person irrespective of the number of persons in the chamber. The ventilation
necessary to satisfy 75% of visitors equalled only about 4 s-1 per person.
Occupants, however, were satisfied with far less. In an array of 38 conditions
of smoking occupancy, the ventilation deemed necessary to satisfy 75% of
visitors under customary conditions of occupancy equalled 17.5 s-1 per person.
For both smoking and nonsmoking conditions, a combination of high temperature
(25.5 Deg C) and humidity (r.h. > 70%) exacerbated the odor problem. During
smoking, carbon monoxide rarely reached dangerous levels, but suspended particulate
matter often reached levels considered unacceptable outdoors. The results
highlight the energy penalty incurred in ventilation for smoking occupancy.
KEYWORDS ventilation requirements, body odour, tobacco smoke
#NO 4829 Indoor air flow and pollutant removal in a room with task
ventilation.
AUTHOR Fisk W J, Faulkner D, Bauman F S, Arens E A
BIBINF UK, AIVC 11th Conference, "Ventilation System Performance",
held 18-21 September 1990, Belgirate, Italy, Proceedings published March
1990, Volume 1, pp 79-98, 5 figs, 4 tabs, 12 refs. #DATE 00:03:1991 in English
ABSTRACT In an experimental facility, we studied the performance of a task
ventilation system designed for use in office buildings. With this system,
occupants can adjust the flow rate and direction of air supplied to their
work space through four floor-mounted supply grills. Air typically exits
the ventilated space through ceiling-mounted return grills. To study indoor
air flow patterns, we measured the age of air at multiple indoor locations
using the tracer gas stepup procedure. To study the intra-room transport
of tobacco smoke particles, cigarettes were smoked mechanically in one workstation
and particle concentrations were measured at multiple indoor locations. Test
variables included the furnishings of the chamber, thelocation(s) of air
supply, supply flow rates, temperatures, and directions, and internal heat
loads. Our major findings were as follows: (1) In most tests, deviations
from a uniform age of air, and a uniform particle concentration, were less
than 30 percent. (2) Some supply air short circuits to the return grillwhen
the air is directed toward the return grill with a high velocity. (3) Low
supply velocities resulted in a floor-to-ceiling displacement ventilation
flow pattern. (4) Directing the supply air toward the occupant, or away from
the center of the four supply grills, typically yielded an age of air at
the occupant's breathing level that was 15 to 25 percent lower than the age
at other breathing-level locations. (5) With low supply velocities and air
directed toward the occupants, tobacco smoke particle concentrations in a
ventilated non-smoking workstation were 50 percent of the chamber-average
concentration.
KEYWORDS pollutant, air flow, office building, occupant control
#NO 4858 Determination of air exchange rates for demand controlled
ventilation.
AUTHOR Saari M
BIBINF UK, AIVC 11th Conference, "Ventilation System Performance",
held 18-21 September 1990, Belgirate, Italy, Proceedings published March
1990, Volume 2, pp 167-176, 1 fig, 3 tabs, 5 refs. #DATE 00:03:1991 in English
ABSTRACT In this paper the required ventilation air flow rates in residences
with different pollutant loads are considered. The calculative study was
carried out by using the load data presented in the literature. The results
of the study were applied in the development and dimensioning of demand controlled
ventilation systems. The first stage of calculations was to determine the
required ventilation air flow rates (range) with different loads for each
type of rooms separately. In the analysis of required ventilation air flow
rates due to materialemissions, the Monte-Carlo method was applied. The second
stage of calculations was to analyse indoor air contaminantconcentrations
in an apartment as a whole using the required air flow rates in room spaces.
The time-dependent occupant behaviour in the apartment was based on a certain
assumption. Calculations with constant air flow rates ventilation were also
done. When considering different load factors; human based odours, theodours
of smoking, humidity loads and contaminant emissions of materials were taken
into account. The required ventilation air flow rates in different load situations
were determined to guarantee good indoor air quality and humidity conditions,
and to prevent health risks due to material emissions, as well. In most calculation
cases it was assumed that indoor air is fully mixed. In addition, the effect
of air flows on 2-dimension contaminant field was analysed.
KEYWORDS air change rate, demand controlled ventilation
#NO 5047 R-2000 indoor formaldehyde monitoring - 1987 update.
AUTHOR Piersol P, Mijailovic A
BIBINF Canada, Energy Mines and Resources, R-2000 Home Program Technical
Report, August 1987, 26pp, 6 figs, 3 tabs, refs. #DATE 00:08: 1987 in English
ABSTRACT As part of the R-2000 Home Program, indoor air quality monitoring
was conducted Canada-wide for a number of pollutants including formaldehyde.
The objective of this report is toreview the R-2000 Home Program formaldehyde
activities to date. A detailed investigation of a select number of Ontario
R-2000 homes identified the following criteria which could create formaldehyde
levels greater than 0.05 ppm: indoor temperatures higher than 21 Deg C, relative
humidity exceeding 50%, tobacco smoke, new furnishings or building materials
containingurea-formaldehyde resin and ventilation systems not meeting the
R-2000 requirements. Monitoring results to date appear to indicate that the
implementation of revised R-2000 ventilation guidelines in 1986 has resulted
in average indoor formaldehyde levels being reduced to less than 0.05 ppm.
Monitoring indicates that when strong formaldehyde sources are present, formaldehyde
levels are somewhat greater than 0.05 ppm, but still less than the 0.10 ppm
short-term action level proposed by the Federal/Provincial Indoor Air Quality
Working Group. This indicates a need to address the issue of controlling
sources of formaldehyde as well as providing good ventilation if levels in
all homes are to be reduced below the 0.05 ppm long-term target.
KEYWORDS formaldehyde, indoor air quality
#NO 5215 Mechanical ventilation in office buildings and the sick building
syndrome. An experimental and epidemiological study.
AUTHOR Jaakkola J J K, Heinonen O P, Seppanen O
BIBINF Denmark, Copenhagen, Indoor Air, No 2, 1991, pp 111-121, 2 figs, 5
tabs, refs. #DATE 00:00:1991 in English
ABSTRACT The effects of mechanical ventilation on the sick building syndrome
(SBS) were studied in an office building with 2150 employees, where the mechanical
ventilation and indoor air quality were commonly blamed for causing symptoms
typical of theSBS (nasal, eye, and mucous membrane symptoms, lethargy, skin
symptoms and headache). The mechanical ventilation rates in the building
were high (mean 26 l/s/person). To test the hypothesis that mechanical ventilation
causes the SBS, a controlled experimental study was carried out by shutting
off the ventilation in one part of the building and reducing the ventilation
rate by 75% and 60% in two areas while leaving one part unaltered as a control.
The experimental reduction of the ventilation rate did not alleviate the
symptoms. On the contrary, the reduction of the ventilation rate caused a
slightbut statistically significant relative increase in symptoms (p < 0.05).
In the cross-sectional analysis of the baseline data the SBS symptoms did
not associate significantly with the ventilation rate (range 7-70 l/s/person).
In the linear regression model, a positive correlation was found between
temperatures above 22 Deg C and the occurrence of symptoms (p < 0.05).
Subjects exposed to environmental tobacco smoke had more symptoms than those
not exposed (p < 0.01). Women reported more symptoms than men (p < 0.001).
In addition, any prior history of allergic diseases (p < 0.001) and a
negative attitude towards the social atmosphere at work (p < 0.001) were
significant determinants of the SBS.
KEYWORDS mechanical ventilation, office building, sick building syndrome
#NO 5426 Introduction to indoor air quality. A self-paced learning
module.
AUTHOR Ritchie I
BIBINF USA, Environmental Protection Agency, Office of Air and Radiation,
July 1991, 120pp. #DATE 00:07:1991 in English
ABSTRACT The Learning Module approaches the broad topic of indoor air quality
by developing an understanding of the general principles needed to recognize,
diagnose, mitigate, and prevent indoor air quality problems. Unit 1 provides
an historical perspective on indoor air quality, presents background information
on the factors which influence indoor air quality, lays the foundation for
evaluating health effects from indoor air contaminants, and discusses general
principles for controlling the indoor air environment. Unit 2 discusses general
principles of measuring indoor air contaminants, identifies standards and
guidelines for ventilation and air contaminants, and describes techniques
which can be used to investigate indoor air quality problems. Finally, Unit
3 provides the basic background needed to establish anindoor air quality
program.
KEYWORDS indoor air quality, formaldehyde, radon, asbestos, tobacco smoke,
combustion product, ventilation rate
#NO 5917 IEA Annex 18/2: Demand controlled ventilating systems.
AUTHOR Mansson L G
BIBINF IEA Energy Conservation in Building and Community Systems Programme,
Executive Committee Meeting, Technical Day, Sophia Antipolis, 2nd June 1992,
135pp + app. #DATE 02:06:1992 in English
ABSTRACT A test programme has been designed to evaluate the performance characteristics
of sensors for the automatic control of ventilation rates. The test programme
consists of two main parts, one being the evaluation of sensor performance
in laboratory tests and the other referring to long term characteristics
of sensors in actual buildings. Included in the present evaluation are nine
different types of humidity sensors, two carbon dioxide sensors and five
mixed gas sensors. The test results indicate that capacitive humidity sensors
are well suited for the control of humidity levels in buildings. The combined
error of linearity, hysteresis and repeatability is normally below 5% relative
humidity at 20 Deg C. The cross-sensitivity to variations in the ambient
temperature and power supply (voltage and frequency) are acceptable and the
cross sensitivity to hydrocarbons, carbon dioxide and tobacco smoke is negligible.
A plastic stripe humidity sensor on the other hand proved unsuitable due
to excessive hysteresis and linearity errors. Carbon dioxide sensors show
acceptable performance for control purposes but sensor calibration and/or
adjustment is a time consuming process. These sensors are sensitive to humidity
below a threshold value. The mixed gas sensors show a mixed behaviour. Some
react strongly to tobacco smoke, some slightly and one hardly at all. The
characteristic curve was determined using a gas cocktail consisting of equal
parts of one alifatic hydro carbon, one aromatic hydro carbon and one aldehyde.
Tests were also made with one component at a time butthere was little difference
in the response to the individual components. All sensors endured the climatic
tests reasonably well. Mechanical vibration on the other hand caused some
of the sensors to break. Radiated electromagnetic fields affected all sensors
and electric shocks, due to a simulated strike of lightning, proved too much
for most of the sensors.
KEYWORDS demand controlled ventilation, sensor
#NO 5962 Healthy building: an energy efficient air conditioned office
with good indoor air quality.
AUTHOR Dickson D, Collins P
BIBINF UK, Air Infiltration and Ventilation Centre, 13th AIVC Conference,
proceedings, held Hotel Plaza Concorde, Nice, France, 15-18 September 1992.
#DATE 15:09:1992 in English
ABSTRACT The NORWEB Headquarters in Manchester, UK, is an air conditioned
energy efficient office building of unusual design, completed in 1988. It
has three stories with overhanging canopies providing solar shading and 21%
solar control glazing. The open plan interior is ventilated by a displacement
system with three twist outlets in the floor to each desk position. A detailed
questionnaire survey showed this to be one of the'healthiest' buildings tested
so far, with a very low 'building sickness symptom score'. Air temperature,
humidity, air speed, fresh air, noise, dust and lighting were monitored and
found to lie within accepted guidelines. Fine dust levels were lower than
outside. Energy costs monitored over three years proved to be low for a building
of this type. The achievement of good indoor air quality combined with energy
efficiency is attributed to good passive design features, the displacement
ventilation system, a limited smoking policy and active participation of
the end user at all stages of the design, construction and management of
the building.
KEYWORDS energy efficiency, air conditioning, office building, indoor air
quality
#NO 6228 Residential indoor air quality guidelines.
AUTHOR Tobin R S, Bourgeau M, Otson R, Wood G C
BIBINF Indoor air quality, ventilation and energy conservation, 5th International
Jacques Cartier Conference, Montreal, Canada, October 7-9, 1992, publisher:
Center for Building Studies, Concordia University, Montreal, Canada, pp 12-26.
#DATE 00:10:1992 in English/French
ABSTRACT Indoor air quality is of prime importance to human health because
we spend >80% of our time indoors. Occupants of indoor environments may
be exposed to a variety of pollutants originating from human activities orpresence
in the home, combustion for heating and cooking, consumer products, furnishings,
building materials and outdoor air. Because of the potentially adverse effects
to human health resulting from exposure to pollutants in the home, the "Exposure
Guidelines for Residential Indoor Air Quality" were developed. Exposure
limits were prepared for the following compounds or groups of compounds:
aldehydes, carbon dioxide, carbon monoxide, formaldehyde, nitrogen dioxide,
ozone, particulate matter, sulphur dioxide, water vapour and radon. In addition,
the guidelines suggest recommendations for controlling exposure to some contaminants
for which the formulation of acceptable exposure ranges was deemed inappropriate
or was not feasible. This group includes: biological agents, chlorinated
hydrocarbons, fibrous materials, lead, pest control products, polycyclic
aromatic hydrocarbons, product aerosols, and tobacco smoke. Review of five
substances (xylenes, toluene,1,4-dichlorobenzene, benzene, and tetrachloroethylene)
to determine potential health risk has revealed the primary route of exposure
through indoor air. They will be considered for guideline development and
possible inclusion in the existing Exposure Guidelines for Residential Indoor
Air Quality. Health and Welfare Canada has an active research program including
a variety of projects: a survey of the occurrence of selected volatile organic
compounds in Canadian residences representing a range of energy efficiencies;
development and evaluation of analytical methods for measurement of human
exposure to airborne organics; a study to measure home dampness and molds
to validate the observed association between respiratory health and indicators
of home dampness; and participation in projects related to energy conservation
and air quality as part of the research program of the Panel on Energy Research
and Development (PERD).
KEYWORDS indoor air quality, health, pollutant
#NO 6421 A pilot study to measure indoor concentrations and emission
rates of polycyclic aromatic hydrocarbons.
AUTHOR Offermann F J, Loiselle S A, Hodgson A T, Gundel L A, Daisey J M
BIBINF Denmark, Indoor Air, No 4, 1991, pp 497-512, 4 figs, 6 tabs, refs.
#DATE 00:00:1991 in English
ABSTRACT Sampling and analytical methods for gas- and particulate-phase polycyclic
aromatic hydrocarbons (PAH) in indoor air were evaluated in a controlled
field study. Using 12-h, 25-m3 samples, gas-phase PAH were collected on XAD-4
resin and analyzed by GC-MS, and particulate-phase PAH were collected in
filters and analyzed for by HPLC with fluorescence detection. Tests were
conducted in homes and office buildings without active combustion sources
and with gas stoves, wood stoves and cigarette smoking as controlled sources.
Indoor concentrations, outdoor concentrations and air-exchange rates were
simultaneously measured. The precisions of the concentrations were evaluated
using collocated sample pairs collected indoors and outdoors. Net emission
rates were calculated for the gas-phase PAH. Net emissions of these compounds
were measured in buildings without active combustion sources. Environmental
tobacco smoke was identified as a significant source of both gas- and particulate-phase
PAH.
KEYWORDS organic compound, air change rates, tobacco smoke, gas cooking,
wood, stove
#NO 6533 Indoor air pollution: a health perspective.
AUTHOR Samet J M, Spengler J D (editors)
BIBINF USA, Johns Hopkins University Press, 1991, 407pp. #DATE 00:00: 1991
in English
ABSTRACT This book provides a comprehensive review of the rapidly enlarging
evidence on indoor air quality and health. The structure of the book reflects
the complexity of the problem of indoor air quality. The book begins with
a perspective on outdoor and indoor air quality. Subsequent chapters address
the sources of indoor air pollution, the levels of pollution in homes, the
assessment of indoor air quality, and the operating characteristics of buildings.
The major topic of the book is the health effects of indoor pollutants. Pollutants
that are specifically considered include carbon monoxide, formaldehyde, other
volatile organic compounds, environmental tobacco smoke, nitrogen dioxide,
radon, and wood smoke. The effects of biologic agents are considered separately.
The topical problem of indoor asbestos is covered, but the health risks do
not receive separate treatment. The occupational hazards of asbestos have
been amply described, and direct evidence on the health risks of indoor asbestos
is unavailable. The remaining chapters of the book address such other important
dimensions of indoor air quality as the control of pollution and its legal
aspects.
KEYWORDS health, indoor air quality
#NO 6544 Volatile organic compounds.
AUTHOR Wallace L A
BIBINF in "Indoor Air Pollution: a Health Perspective", edited
by J M Samet and J D Spengler, USA, Johns Hopkins University Press, 1991,
pp 253-272. #DATE 00:00:1991 in English
ABSTRACT Organic chemicals found indoors may be implicated in either acute
health effects (sick building syndrome) or in chronic effects (cancer). However,
the mechanisms of action are largely unknown and must await further research
in neurobehavioural or immune system response, pharmacokinetics, and mutagenicity
studies of complex mixtures. We have good knowledge of indoor concentrations
and major sources of most VOCs, particularly nonpolar VOCs that are not extremely
volatile. Nearly all of these are usually at higher concentrations indoors
than outdoors, with short-term indoor peaks one hundred to one thousand times
greater than outdoors. Preliminary data on SVOCs indicate that 80 percent
or more of personal exposure topesticides is from indoor sources. Little
is known concerning concentrations and major sources of polar organics (oxygenated
compounds), high-volatility nonpolar organics (vinyl chloride, methylene
chloride, and others), or particle bound organics (PAHs, dioxin and furans).
Major sources of indoor organics include consumer products (deodorizers,
solvents, and others), personal activities (smoking, cleaning, using hot
water, wearing dry-cleaned clothes, and others), and building related products
and processes (paints, adhesives, caulking, fabrics, custodial cleaning,
and pest control). Few details are known regarding emission rates of organics
from the myriad different consumer products.
KEYWORDS organic compound, pollutant
#NO 6655 Chronic sidestream cigarette smoke exposure causes lung injury
in rabbits.
AUTHOR Witten M L, Joseph P M, Lastz R C, Lazarus D S, Jung W K, Hales C
A
BIBINF Indoor Environment, No 1, 1992, pp 341-347, 2 figs, 2 tabs, 34 refs.
#DATE 00:00:1992 in English
ABSTRACT The effects of sidestream cigarette smoke (a 15-min exposure per
day for 20 days) were determined on markers of lung injury in New Zealand
white rabbits and a control group. Electron microscopy demonstrated that
the airway mucosa of the rabbits was infiltrated by eosinophils, and light
microscopy showed focal clusters of neutrophils in perivascular and capillary
spaces. It is concluded that sidestream cigarette smoke can induce lung injury.
KEYWORDS tobacco smoke, indoor air quality
#NO 7016 Mechanical Ventilation System with Heat Exchanger in One
Room - Low Cost Mechanical Ventilation System.
AUTHOR Egedorf M
BIBINF UK, Air Infiltration and Ventilation Centre, 14th AIVC Conference, "Energy
Impact of Ventilation and Air Infiltration", held Copenhagen, Denmark,
21-23 September 1993, proceedings, pp95-96. #DATE 21:09:1993 in English
ABSTRACT A new miniature mechanical ventilation system with both supply and
extract air and an air-to-air heat exchanger has been developed in Great
Britain and Denmark. The system which isintended to ventilate a single room
has the dimensions of a shoebox and can be placed/installed on the inside
wall in an existing air vent. The system can operate with two air flows,
40 or 70 m3/h. At the low speed the noise is insignificant, intended to be "not
disturbing" in sleeping rooms. Switching between the two speeds can
be done either manually or automatically controlled by the relative humidity
of the extracted air. The system is also provided with filters. This spring
we will perform different measurements in the laboratory to check the system
performances, for instance volume flow rate, draught, short circuiting of
air, efficiency of the heat exchanger and noise. In the paper we will report
the results of the tests. Maybe this system is the long desired cheap and
no-problems solution of mould-problems in sleeping rooms or tobacco smoke
in offices?
KEYWORDS mechanical ventilation, heat exchanger
#NO 7121 Effectiveness of ventilation and other controls in reducing
exposure to ETS in office buildings.
AUTHOR Hayward S B, Liu K-S, Alevantis L, Shah K, Loiselle S, Offermann F
J, Chang Y-L, Webber L
BIBINF Finland, Helsinki, Indoor Air '93, proceedings of the 6th International
Conference on Indoor Air Quality and Climate, 1993, Vol 5, pp 509-514. #DATE
00:07:1993 in English
ABSTRACT A study was conducted in government-owned office buildings in California
to evaluate the effectiveness of various control measures such as exhaust
ventilation and physical barriers for protecting non-smokers from environmental
tobacco smoke (ETS) generated by smoking in designated areas in the building.
In each of the buildings, smoking patterns were logged. Components of ETS
were measured in the smoking area and in adjacent non-smoking areas. Tracer
gas measurements are used to follow the movement of air between smoking and
non-smoking areas, and to measure overall ventilation rates. Results of tracer
gas and ETS measurements were in general agreement. Concentrations in both
smoking and non-smoking areas depended on the type of engineering controls
used. Tracer gas measurements, along with a ventilation system evaluation,
were useful in assessing protection of non-smokers from ETS generated in
the smoking areas.
KEYWORDS tobacco smoke, office building, tracer gas
#NO 7150 Indoor airflow and pollutant removal in a room with desktop
ventilation.
AUTHOR Faulkner D, Fisk W J, Sullivan D P
BIBINF USA, Ashrae Transactions, 1993, Vol 99, Part 2, Preprint, 8pp, 2 figs,
2 tabs, refs. #DATE 00:07:1993 in English
ABSTRACT In a furnished experimental facility with three workstations separated
by partitions, we studied the indoor airflow patterns and tobacco smoke removal
efficiency of a desktop task ventilation system. The task ventilation system
permits occupant control of the temperature, flow rate, and direction of
air supplied through two desk-mounted supply nozzles. In the configuration
evaluated, air exited the ventilated space through a ceiling-mounted return
grille. To study indoor airflow pattens, we measured the age of air at multiple
indoor locationsusing the tracer gas step-up procedure. To study the intraroom
transport of tobacco smoke particles and the efficiency of particle removal
by ventilation, a cigarette was smoked mechanically in one workstation and
particle concentrations were measured at multiple indoor locations, including
the exhaust airstream. Test variables included the direction of air supply
from the nozzles, supply nozzle area, supply flow rate and temperature, percent
recirculation of chamber air, and internal heat loads. Our major findings
are as follows: 1) in tests with the nozzles pointed toward the occupants,
100% outside air supplied at the desktop, and air supply rates of approximately
85 cfm (40L/s) per workstation, the age of air at the breathing level of
ventilated workstations was approximately 30% less than the age of air that
would occur throughout the test space with perfectly mixed indoor are; 2)
with smaller air supply rates and/or air supplied parallel to the edges of
the desk, ages of air at breathing locations were not significantly lower
than the age with perfect mixing; and 3) indoor tobacco smoke particle concentrations
at specific locations were generally within 12% of the average measured indoor
concentration, and concentrations of particles in the exhaust airstream were
not significantly different from the concentration of particles at breathing
locations.
KEYWORDS air flow, pollutant, occupant behaviour, workplace ventilation system
#NO 7338 Indoor air as a source of annoyance.
AUTHOR Cain W S.
BIBINF in "Environmental Annoyance : Characterization, Measurement,
and Control", edited by Harry S Koelega, proceedings of the International
Symposium inEnvironmental Annoyance, held at the Conference Centre Woudschoten,
Netherlands, 15-18 Sept 1986, pp189-200, 6 figs, 17 refs. #DATE 00:09:1986
in English
ABSTRACT Describes human reaction to odour in the indoor environment, particularly
tobacco smoke. Whereas the visitor to a smoking space will assess air quality
on the basis of odour, the occupant in the space will assess it largely on
the basis of irritation. Once irritation begins, it tends to increase over
time. Despite the sensitivity of the occupant to the irritation caused by
environmental tobacco smoke, the visitor to a space is still the more critical
judge of the need for ventilation.
KEYWORDS indoor air quality, occupant reaction, odour.
#NO 7861 Respiratory symptoms and housing characteristics
AUTHOR Spengle J, Neas l, Nakai S, Dockery D, Speizer F, Ware J, Raizenne
M
BIBINF #DATE 00:00:1994 in English
ABSTRACT A health and housing questionnaire was administered to children,
ages 9-11, living in 24 communities in the United States and Canada. Logistics
regression analysis examined the relationship between respiratory health
symptoms (bronchitic, asthmatic, and lower respiratory) and housing factors.
The health risks (expressed as relative odds) were controlled for gender,
parental asthma, parental chronic obstructive pulmonary disease and parental
education, as well as between-city differences. Lower respiratory symptoms
had significantly higher odds ratios reported in older homes (1.12), homes
with smokers (1.24) air conditioners (1.14) air cleaners (1.37) and humidifiers
(1.47). Home dampness (1.48) and the individual mold and water variables
were all significantly associated with increased symptoms. similar results
were reported from bronchitic remained significant after controlling for
childhood atopy.
KEYWORDS respiratory illness, health, questionnaire, air cleaning
#NO 8024 Natural ventilation strategies to mitigate passive smoking
in homes.
AUTHOR Kolokotroni M, Perera MDAES
BIBINF UK, Air Infiltration and Ventilation Centre, 1994, "The Role
of Ventilation", proceedings of 15th AIVC Conference, held Buxton, UK,
27-30 September 1994, Volume 2, pp759-770.
ABSTRACT This paper investigates possible natural ventilation strategies
to reduce exposure to environmental tobacco smoke (ETS) in dwellings. Particular
attention is paid to the migration of tobacco smoke from the living room
(usually the smoking room) to the bedrooms which may be occupied by children.
This addresses an area of current concern regarding the possible association
between passive smoking and adverse health conditions; in particular the
link between parental smoking and respiratory illness in children. The study
used the multizoned airflow prediction program BREEZE to evaluate the movement
of tobacco smoke from the smoking rooms to the bedrooms in typical detached,
semi-detached and terraced dwellings for a variety of natural ventilation
strategies. Typical smoking patterns were emulated and contaminant movements
analysed, taking into account factors such as wind speeds and direction and
air temperatures. Some of the results obtained were compared with limited
full-scale measurements acquired elsewhere to provide the necessary confidence
in the predictions. Controlling pollutant concentration by ventilation can
bean energy intensive process, especially during the heating and cooling
season. Since almost all dwellings in the U.K. are naturally ventilated,
providing optimum ventilation with minimum ventilation heat loss is of concern
only during the heating season. Results from the study indicate three possible
strategies to mitigate the effect of passive smoking in dwellings; two which
could be used during the heating season and one for theremaining times of
the year.
KEYWORDS (natural ventilation, passive smoking, residential building, respiratory
illness)
#NO 8091 Demand ventilation - a major potential for energy saving
is wasted. Bedarfslueftung - ein grosses Energie-Sparpotential liegt
brach.
AUTHOR Meier S
BIBINF Germany, HLH, Vol 45, N09, 1994, pp 459-465, 12 figs, 8 refs, in German.
ABSTRACT Wherever room occupancy varies considerably (lecture halls, auditoria,
concert halls, theatres, gymnasia, shopping centres, restaurants, etc.),
the supply of external air should be provided in line with the requirement
(requirement control, air quality control). Experience has shown that it
is possible to reduce the operating period and thus the energy consumption
of air-conditioning systems by up to 50%, compared to operation by means
of a timer programme. Mixed gas and CO2 sensors are suitable references for
control purposes. The CO2 concentration is an indicator forthe presence of
people. Mixed gas sensors also detect the vapours emitted by people, tobacco
smoke and emissions from materials. Mixed gas and CO sensors are currently
used successfully in many systems. At present, a Swiss company is working
intensively on the further developmentof an air quality sensor based on mixed
gas sensors and on the issuance of application know-how.
KEYWORDS (demand controlled ventilation, auditorium, theatre, outdoor air)
#NO 8256 ETS control requires separate areas, high negative pressure
AUTHOR Anon
BIBINF USA, Indoor Air Quality Update, December 1994, pp 2-5, 1 tab.
ABSTRACT Summary of a study conducted by researchers from the Californian
Department of Health Services which suggested that to prevent environmental
tobacco smoke (ETS) from infiltrating into non-smoking areas, buildings require
separate smoking areas with outside exhaust, and that these areas need to
be kept at -7 Pascals (Pa) relative to the non-smoking areas. Twenty three
buildings were investigated, fourteen of which had enclosed smoking.
KEYWORDS tobacco smoke, pollutant, air infiltration, exhaust
#NO 8469 Mutagens in indoor air particulate.
AUTHOR Nardini B, Granella M, Clonfero E
BIBINF Italy, proceedings of Healthy Indoor Air '94, held Anacapri, Italy,
6-8 October 1994, pp 99-104.
ABSTRACT Twenty-seven extracts of airborne particulate from domestic environments,
both in the absence of sources of pollution and during activities such as
smoking tobacco, using a fireplace, and cooking using grills and barbecues,
and eight control samples of outdoor particulate were tested using the Salmonella/microsome
assay on strains TA98 and TA98NR. Dust levels and mutagenic activity in the
indoor environments turned out to be very low in the absence of polluting
sources. The specific mutagenic activity of indoor dusts ranged from 22 and
137 revertants/mg, with a contribution of nitroarene compounds of about 50%,
indicating that, in city indoor air, the main cause of background particulate
pollution is very probably penetration of traffic fumes from the outside.
The presence of autochthonous pollution sources greatly increased indoor
just levels, especially during cooking operations, which reached 25.5 and
31.6 mg/m3. The particulate produced by the various indoor polluting sources
showed varying specific mutagenic activities. The highest values were found
for fumes produced by burning charcoal and wood, smoking tobacco, and cooking
foods with high animal protein contents. Mutagens responsible were mainly
direct-acting in the case of fumes from burning wood or charcoal, and required
mammalian metabolic activation in the case of fumes from tobacco and meat,
with a lower contribution (maximum 33%) of nitroarenes than in urban particulate.
KEYWORDS particulate, tobacco smoke, dust
#NO 8530 Effectiveness of Ventilation in 23 designated smoking areas
in California office buildings
AUTHOR Alevantis L E.
BIBINF USA, paper presented at Ashrae: IAQ '94, 26 pp, 2 figs, 6 tabs, refs.
ABSTRACT We conducted a field study in 23 designated smoking areas in 22
California city and county office buildings to evaluate the effectiveness
of various ventilation and other controls to limit leakage of environmental
tobacco smoke (ETS) from smoking to adjacent non-smoking areas. The controls
we studied included: 1) physical separation of smoking areas ranging from
complete isolation of smoking areas by walls and closed doors, including
return air separation, to open, adjacent and/or continuous smoking/non-smoking
areas, 2) local exhaust ventilation, and 3) varying amounts of outdoor air.
Our results indicate that the most effective smoking area design is that
of an enclosed smoking area with no air recirculation to non-smoking areas,
exhaust to the outside and a negative air pressure relative to adjoining
non-smoking areas. Our limited field data indicate that for negative pressures
above 7 Pa (0.03 inch of water gauge) a 99.9% dilution of smoking-room air
was achieved in the non-smoking areas. However, further research is required
to determine the optimum negative pressure requirement for controlling ETS
in smoking areas. Furthermore, enclosed smoking areas without an exhaust
to the outside offer only moderate protection to non-smokers in adjoining
areas, whereas open, adjacent and/or continuous smoking/non-smoking areas
offer moderate to no protection at all to occupants of the non-smoking sections.
KEYWORDS environmental tobacco smoke, smoking lounge, smoking area, local
ventilation, local exhaust, tracer gas, nicotine, office building.
#NO 8613 Customer benefits of demand-based ventilation in a restaurant
AUTHOR Meier S
BIBINF Sweden, Proceedings of the 4th International Symposium on Ventilation
for Contaminant Control, Ventilation '94, held in Stockholm, September 5-9,
1994, Arbetsmiljoinstitutet, 1994:18, Part 1, pp 527-532.
ABSTRACT In a restaurant with a "demand-based" ventilation system,
the air quality in the dining area is continually monitored by an air quality
sensor and the fan stages are switched automatically on the bases of the
sensor signal. Since the greatest irritation in restaurants is tobacco smoke,
the air quality sensors used are of the "mixed-gas" type. The study
which has been in progress since December 1993 shows the following: - By
comparison with manual fan control, energy savings of over 25% can be achieved
with a ventilation system controlled on the basis of air quality demand.
- There is a high correlation between the air quality measured with mixed-gas
sensors and the odour load in the room (people, smoking, ventilation rate).
- According to the restaurant manager, there has been a significant reduction
in complaints by guests since the demand-based ventilation system has been
in operation. Not only were there fewer complaints about air quality while
people were smoking, but also fewer problems with the air supply system (draft).
- The experience gained in the course of this investigation indicates that
the outside air flow rate of 36 m3/h per person specified in many countries
is not sufficient to produce a continuously acceptable level of air quality
for the non-smokers present.
KEYWORDS demand controlled ventilation, commercial building, indoor air quality,
sensor, tobacco smoke, odour
#NO 8617 Ventilation effectiveness in the case of wind-forced ventilation
AUTHOR Yamanaka T, Narasaki M, Kido K
BIBINF Sweden, Proceedings of the 4th International Symposium on Ventilation
for Contaminant Control, Ventilation '94, held in Stockholm, September 5-9,
1994, Arbetsmiljoinstitutet, 1994:18, Part 2, pp 539-544.
ABSTRACT In this paper, the ventilation effectiveness in the case of wien-forced
ventilation is investigated through experiment in wind tunnel. The cubic
model enclosure with two circular openings is set up in the middle of closed-jet
wind tunnel. The ventilation efficiency is measured by tracer gas method.
The effect of location of openings and the wind direction on ventilation
efficiency are examined, and the air flow patterns and the concentration
of tracer gas visualized with tobacco smoke lit up by laser light sheet.
As a result, it is turned out that the air change efficiency ranges from
0.4 to 0.57 around 0.5 of perfect mixing and the air flow patterns and distribution
of tracer gas depend upon the location of windward opening and the air flow
direction of supply air through the opening.
KEYWORDS ventilation effectiveness, wind effects, wind tunnel, tracer gas
#NO 8732 Indoor airflow and pollutant removal in a room with floor-based
task ventilation: results of additional experiments.
AUTHOR Faulkner D, Fisk W J, Sullivan D .
BIBINF UK, Building and Environment, Vol 30, No 3, 1995, pp 303-332, 6 figs,
3 tabs, 15 refs.
ABSTRACT A laboratory-based study of the performance of a floor-based task
ventilation system designed for use in office buildings has been completed.
With the task ventilation system, occupants can adjust the flow rate and
direction of air supplied to their work space through floor-mounted supply
grilles. Air exits the ventilated space through a ceiling-mounted return
grille. To study indoor airflow patterns, the age of air at multiple indoor
locations was measured using the tracer gas step-up procedure. To study the
intra-room transport of tobacco smoke particles, cigarettes were smoked mechanically
in one workstation and particle concentrations were measured at multiple
indoor location. Test variables included supply flow rates, temperatures,
supply directions, and internal heat loads. Multiple floor supply units were
in operation simultaneously. During all tests, the ventilation system supplied
100% outside air. Our major findings are as follows. (1) Deviations from
a uniform age of air, and a uniform particle concentration, were generally
less than 30%/ (2) With two floor-supply units operating and supply air directed
toward the occupant, the age of air in the breathing zone was about 20-40%
less than the age of air that would occur in the room if the air was perfectly
mixed. (3) With two floor-supply units operating, the air appears to travel
from the floor to the ceiling in a piston-like flow pattern. (4) With three
floor-supply units operating, a two-zone flow pattern, with a piston-like
flow in the lower region of the room and mixing in the upper region, was
evident at some operating conditions. (5) A strong (r2=0.81) correlation
was found between the rate of change in the average age of air with height
and two factors hypothesized to be determinants of the indoor airflow pattern.
(6) Workstations without a cigarette smoking machine and with an operating
task ventilation system were not significantly protected from tobacco smoke
in an adjacent workstation.
KEYWORDS air flow, pollutant, occupant control
#NO 8767 Design instructions for smoking room. Tupakointitilojen suunnitteluohje.
AUTHOR Karjalainen T.
BIBINF Finland, Teknillinen korkeakoulu, LVI-laboratorio, Raportti B39, Espoo
1995, 95 pp, in Finnish.
ABSTRACT A new tobacco law will be valid after 1st March 1995 in Finland.
According to the new law, smoking will be prohibited inside all the public
buildings. Also, smoking will be forbidden in working environments in public
and common spaces as well as in spaces for customers. Smoking may be allowed
in a smoking room that is arranged especially for this purpose. This requires
that tobacco smoke may not spread to the non-smoking areas. The owner of
the public building or the employer is not committed to arrange smoking rooms.
A smoking room has to be underpressured across the envelope in relation to
the non-smoking areas so that the airflows that may transport smoke can be
prohibited. The removal of the smoke can be performed using exhaust ventilation
or filtration. Structurally, a smoking room has to be tight enough to ensure
that the building s pressure conditions can be controlled in all circumstances.
Smoking can be allowed in a separate smoke room, partitioned smoke room,
or in a single person s work room. Also, a so-called movable smoking room
with integrated filtration equipment can be installed as a smoking room.
This study introduces design instructions for architects and HVAC-designers
that can be used in designing and building smoking room solutions that can
be accepted by the new tobacco law.
KEYWORDS tobacco smoke, building code, ventilation rate, pollutant
#NO 8768 How much does environmental tobacco smoke contribute to the
Building Symptom Index?
AUTHOR Raynol A, Burge P S, Robertson A, Jarvis M, Archibald M, Hawkin D.
BIBINF Denmark, Indoor Air, No 5, 1995, pp 22-28, 1 fig, 3 tabs, refs.
ABSTRACT Environmental tobacco smoke (ETS) has been identified as one of
the factors associated with the symptoms off the sick building syndrome (SBS).
We investigated the role of ETS in an office building during the phased introduction
of a smoking ban. Over a two-year period we measured symptoms using a validated
questionnaire, environmental nicotine levels and salivary cotinine as a biological
marker of nicotine absorption in a stratified systemic sample of 375 office
employees (91% response rate). In addition, 26 persons from a non-smoking
office were studied as a control group. This report describes the findings
derived from a cross-sectional analysis of the initial baseline data. Amongst
the validated non-smokers, symptoms increased with increasing nicotine exposure
from ETS (r=0.165 p,0.01), supporting the role of ETS in the SBS. Smokers
reported significantly fewer symptoms than non-smokers, as has been found
before, but were exposed to higher levels of airborne nicotine as expected.
We suggest that this factor, along with the misclassification of smoking
status, may have obscured an association between ETS exposure and the SBS
in previous studies. An analysis of the findings after implementation of
the smoking ban should provide further information on how much of the SBS
is attributable to ETS in this study population.
KEYWORDS tobacco smoke, sick building syndrome, office building
#NO 8859 Naturally ventilating UK non-domestic buildings: status and
future policy
AUTHOR Perera M D A E S, Shaw M R, Treadaway K.
BIBINF Canada, proceedings Indoor Air Quality, Ventilation and Energy Conservation
in Buildings , Second International Conference, held May 9-12, 1995, Montreal,
edited by Fariborz Haghighat, Volume I, pp273-280.
ABSTRACT Increased concern over the adverse environmental impact of energy
use has encouraged the design and construction of energy efficient buildings,
and many are suited to natural ventilation. In the temperate UK climate,
naturally ventilated buildings can provide year round comfort, with good
user control, at minimum capital cost and with negligible maintenance. The
principle of good ventilation design is to build tight - ventilate right
. That is, to minimise uncontrolled (and, usually unwanted) infiltration
by making the building envelope airtight, while providing adequate fresh
air ventilation in a controlled manner. It is necessary to emphasise that
a building cannot be too tight - but it can be underventilated. This paper
shows that there is considerable scope for making UK buildings tighter and
indicates the level of benefits that will accrue. UK activity in this area
is identified, including proposed statutory control in the form of revised
Building Regulations for England and Wales, which will address issues of
tightness for the first time. Information is available on ventilation requirements
necessary to satisfy safety and health criteria. However, criteria relating
to comfort, especially those associated with odour, metabolic CO2, and summer
overheating are still being investigated. This paper sets out current thinking
in this area, including policies relating to minimising effects of tobacco
smoking in public and commercial buildings. The paper concludes by identifying
currently available UK design guidance natural ventilation. Various instruments
which are underpinning these changes, such as revisions to the Building Regulations
for England and Wales, codes and standards professional guidance and support
for policy-interests are identified.
KEYWORDS natural ventilation, energy efficiency, thermal comfort
#NO 9242 Effectiveness of ventilation and other controls in reducing
exposure to environmental tobacco smoke in office buildings.
AUTHOR Hayward S B, Alevantis L E, Liu K-S
BIBINF USA, California Dept of Health Services, November 1995, 66pp + app.
ABSTRACT To date there has been insufficient research on how to design and
operate smoking areas to minimise exposure of non-smokers to ETS. The issue
was addressed by evaluating the effectiveness of various engineering controls
in 23 designated smoking areas within 22 Californian public office buildings
to protect non-smokers form ETS generated within smoking areas. 111 buildings
were selected initially and 22 for intensive study, which were monitored
over a three to four day period. Based on the results, the researchers found
that the most effective strategy to minimize air movement from smoking areas
to non-smoking areas was that of a designated enclosed smoking area with
the following characteristics: a) full isolation from surrounding spaces
by a closed door and walls that penetrate any suspended ceilings, b) operation
of a mechanical exhaust fan that provides sufficient airflow to maintain
a negative pressure with respect to surrounding spaces, including adjoining
rooms and ceiling cavities, and c) no recirculation of air from the smoking
area to non-smoking areas. The limited data indicated that for negative pressures
above 7 Pascal, a 99.9% dilution of smoking-room air was achieved in non-smoking
areas. However, further research was required to determine the optimum negative
pressure requirements for controlling ETS in smoking areas.
KEYWORDS tobacco smoke, office building, ventilation strategy
#NO 9243 Environmental tobacco smoke and lung cancer in nonsmoking
women: a multicenter study.
AUTHOR Fontham E T H, Correa P, Reynolds P, et al
BIBINF J. American Medical Association, Vol 271, No 22, 1994, pp 1752-1759,
8 tabs, 50 refs.
ABSTRACT The objective was to determine the relative risk (RR) of lung cancer
in lifetime never smokers associated with environmental tobacco smoke (ETS)
exposure. The survey analysed 653 cases of female lifetime never smokers
with histologically confirmed lung cancer and 1253 controls for women aged
65 years and older. Tobacco use by spouse(s) was associated with a 30% excess
risk of lung cancer. An increasing RR of lung cancer was observed with increasing
pack-years of spousal ETS exposure, such that an 80% excess risk of lung
cancer was observed for subjects with 80 or more pack-years of exposure from
a spouse. The excess risk of lung cancer among women ever exposed to ETS
during adult life in the household was 24%; in the workplace, 39%; and in
social settings, 50%. When these sources were considered jointly, an increasing
risk of lung cancer with increasing duration of exposure was observed. At
the highest level of exposure, there was a 75% increased risk. No significant
association was found between exposure during childhood to household ETS
exposure from mother, father, or other household members; however, women
who were exposed during childhood had higher RRs associated with adult-life
ETS exposures than women with no childhood exposure. At the highest level
of adult smoke-years of exposure, the ORs for women with and without childhood
exposures were 3.25 and 1.77 respectively. Concludes that exposure to ETS
during adult life increases risk of lung cancer in lifetime nonsmokers.
KEYWORDS lung cancer, tobacco smoke, passive smoking
#NO 9474 Exposure to environmental tobacco smoke and female lung cancer.
AUTHOR Du Y, Cha Q, Chen X, Chen Y, Lei Y, Xue S
BIBINF Indoor Air, No 5, 1995, pp 231-236, 3 tabs, refs.
ABSTRACT A registry-based case control study, involving 120 cases (28 males,
92 females) of lung cancer deaths, was conducted in 1985 in the city of Guangzhou
to investigate whether lifestyle factors are associated with an increased
incidence of lung cancer in never-smoking individuals. The cases were matched
with two control groups which consisted of non-respiratory-disease-related
deaths or non-respiratory-related cancer deaths. Lifestyle factors assessed
in the study include: personal history of nonmalignant respiratory diseases,
practice of fresh vegetable consumption, lifetime occupation and occupational
exposure histories, exposure to ETS, degree of indoor air pollution, general
conditions of home residence, cooking practices and environments, and family
history of cancer. Conditional logistic regression analysis demonstrated
a negative association between fresh vegetable consumption and lung cancer
risk in both sexes, suggesting that vegetables may exert a protective effect
against lung cancer in humans. In males, elevated risks were found between
lung cancer and occupational exposure. In females, indoor air pollution and
kitchen environment were associated with risk of lung cancer. No statistically
significant association was observed between lung cancer and all other factors
examined, including exposure to ETS. A second case-control, study was performed
in 1986 to investigate the possible association between spousal smoking and
lung cancer deaths. Cases consisted of 75 never-smoking females and the two
control groups consisted of 126 cases of deaths due to tumors except lung
cancer. When cases were matched against"death-unrelated-to-tumor" controls,
the odds ration [OR] for ETS exposure was 1.19, as gauged by whether or not
there was ETS exposure;0.72 and 1.62, when ETS was assessed based on exposure
to less than 20 or to 20 or more cigarettes/day. When ETS exposure was measured
by smoking years .
KEYWORDS tobacco smoke, lung cancer, health
#NO 9562 Chemical indoor air quality control.
AUTHOR Moncada Lo Giudice G, Salvetti F, Scarano E, de Santoli L
BIBINF Healthy Buildings 95, edited by M Maroni, proceedings of a conference
held Milan, Italy, 10-14 September 1995, pp 773-779, 6 figs, refs.
ABSTRACT The indoor air quality IAQ is of fundamental importance with regard
to the evaluation and certification of healthy buildings. Because only precise,
accurate and statistically controlled analytical results allow conclusions
to be drawn about the quality of air and the risks related to chemicals,
quality assurance for air analysis is the object of advanced research. The
decrease of air infiltration existing in modern buildings, due to the presence
of indoor sources of contaminants emitted by materials, the increase of outdoor
polluted air, and the problems related to ventilation energy costs, assign
a primary consideration in ventilation engineering. Monitoring and controlling
the mechanical ventilation is the main reason to develop suitable sensors,
since IAQ cannot be measured objectively, the concept for acceptable air
has been defined. This applies to air which does not contain any known contaminants
in harmful concentrations and which is accepted without complaint by more
than 80% of those people exposed to it . Among organic substances those with
molecular weight greater than 300 are generally odourless, and even if potent
olfactory stimuli derived from some substances can be perceived at very low
concentrations, they may not be detected by existing instruments. Olfactory
sensitivity often is able to detect potentially harmful substances at concentrations
below dangerous levels and therefore able to eliminate them. It is important
to consider odour as a IAQ indicator because a sensory approach (odours and
irritations) has a fundamental role for the IAQ characterisation, being a
complementary method of the traditional physic, chemical and microbiological
studies utilised to measure the exposure (Kirchner et al., 1994). Odours
and irritants thresholds, however, because of a poorly available systematic
review, may vary by several orders of magnitude - and further studies must
be carried out in order to determine more precise indications. Although the
perceived indoor air quality presently can only be measured by means of test
subjects rather than with measuring instruments, reference to this approach
is nevertheless appearing in HVAC ventilation standards (CEN, 1994); critical
review showed that these standards could be based on scientific definitions
to allow measurable outcomes indicating adverse effects on comfort, such
as annoyance and irritation as a function of dilution ventilation (Rehva,
1995). A look at the limitations of present IAQ guidelines suggests a promising
alternative approach for judging the acceptability of IAQ based on antropic
gases (CO2 and/or NH3) monitoring as an integrated measure of all airborne
contaminants present in ambient air, to do it the IAQ guidelines can be based
on both specific contaminants of pollutant mixtures and global presence of
contaminants in the mixtures (Light et al, 1992). The possibility to apportion
contaminants to major classes of emission sources, is generally obtained
using a sensory panel, CO and CO2 measurements. Many studies have apportioned
the perceived IAQ degradation to three categories: occupants, smoking and
building materials including HVAC system. CO serves as a surrogate for cigarette
smoking, CO2 for bioeffluents, but presently only sensory measures can significantly
indicate the importance of the HVAC system and building materials as contaminant
sources (Fanger, 1988). Unfortunately, the relationship of the sensory responses
to physical-chemical measures is not clear. In particular, nonlinearity and
thresholds of sensory responses should be taken into account when identifying
sources quantitatively (Batterman et al, 1995, Pejtersen et al, 1993). The
concentration of CO2 in a room remains a subjective variable for the evaluation
of IAQ, even though its value can be defined exactly. Except for particular
boundary conditions, no relationship (Persily, 1993) can be found between
the CO2 concentration in a room and the IAQ perceived by the human nose.
Otherwise, first one substance and then another would dominate the sense
of smell. It is therefore of little significance to measure concentration
of individual gas selectively, leading to the assumption that the gas mixture
must be evaluated as a whole. That is what the mixed gas sensors do.
KEYWORDS indoor air quality, health, sensor
#NO 9635 Natural ventilation in the United Kingdom: design issues
for commercial and public buildings.
AUTHOR Perera M D A E S, Gilham A V, Clements-Croome T D J
BIBINF UK, Building Serv Eng Res Technol, Vol 17, No 1, 1996, pp 1-5, 2 figs,
15 refs.
ABSTRACT The principle of good design for natural ventilation is to "build
tight - ventilate right". A building cannot be `too tight', but it may
be under-ventilated. There is considerable scope for making UK buildings
tighter. However, simpler techniques need to be developed (especially in
large non domestic buildings) to identify envelope tightness and associated
leakage paths. Also guidance needs to be provided on constructing tighter
envelopes. Studies necessary to assess the implication of tighter buildings
are described. Sufficient information is available on ventilation requirements
necessary to satisfy safety and health criteria. However, criteria relating
to comfort, especially those associated with odour, metabolic CO and summer
overheating need to be investigated. The paper also discusses minimising
the effects of tobacco smoke and controlling other internally generated pollutants.
Guidelines for natural ventilation design may conflict with other design
or climate-responsive strategies, future work should address this, and address
issues such as ventilation openings (to provide both "background" and "rapid" ventilation)
and design for deeper, naturally ventilated buildings.
KEYWORDS natural ventilation, commercial building, public building, air leakage
#NO 9723 Investigation of air quality problems in UK public houses.
AUTHOR Currie J, Capper G
BIBINF France, Ecole Nationale des Travaux Publics de l'Etat, November 1994,
proceedings of the European Conference on Energy Performance and Indoor Climate
in Buildings, held Lyon, France, 24-26 November 1994, Vol 3, pp 1044-1047,
2 figs, 5 refs.
ABSTRACT An assessment was undertaken on six different public houses in the
north of England and southern Scotland with the aim of recognising features
of their construction and operation where environment impact had been reduced,
what improvements could be made to accommodate best environment practice,
and to raise awareness of the adverse effect of buildings on the environment.
Air quality assessments in each establishment identified potential problems
in respect of the trading design approach to ventilated spaces. Selected
environmental tobacco smoke (ETS) surrogates (CO,NOx) were measured together
with CO2 as a general air quality indicator during a 3 month period using
a photoacoustic multi-gas analyser. All premises were installed with manually
controlled mechanical displacement ventilation systems. The traditional approach
to air quality problems arising from ETS has been one of reaction ventilation
when smoke levels were high, resulting generally in under-ventilation of
the space or, in some establishments where the smoke problem was perceived
as being high, over-ventilation where the systems are operated continuously
with a subsequent impact on building energy use. This has been exacerbated
by recent anti-smoking lobbyists success in persuading the Environmental
Health Department of the local Councils to prosecute operators of excessively
smoky public houses.
KEYWORDS indoor air quality, public building, tobacco smoke, carbon dioxide,
displacement ventilation
#NO 9845 French ventilation system performances in residential buildings.
Millet J-R, Villenave J G, Riberon J
UK, Air Infiltration and Ventilation Centre (AIVC), 1996, proceedings of
17th AIVC Conference, "Optimum Ventilation and Air Flow Control in Buildings",
Volume 1, held 17-20 September 1996, Gothenburg, Sweden, pp 167-173.
The comparison of the performance of ventilation systems must take into account
different issues. For indoor air quality, different kinds of pollutant sources
have to be defined. To make an evaluation of the results, the best approach
is to consider the people exposure. Four generic pollutants are taken into
account: rooms components or furniture, human metabolism, cooking activities,
passive smoking. As the definition of the unit for each pollutant is free,
it is useful for their comparison to press them on a common "normalised" basis.
This enables to make a distinction between the simulations based on generic
pollutants and their interpretation which could be derived for many kinds
of pollutants without having to do additional calculations as far as the
considered pollutant follows the conventional patterns. The pressure difference,
for example can be related to radon issues as to running of some heat appliances.
The room parameters are mainly related to humidity issues as condensation,
mould growth or house dust mites. For energy issues, a distinction has to
be made between the direct energy use (fans) and the heat needs due to ventilation.
Such a methodology has been defined within the IEA annex 27 project. After
a presentation of the different parameters taken into account, we describe
the computer code SIREN95 developed at CSTB in order to obtain the required
results and we present a sensitivity analysis for the basic ventilation system
used in France (mechanical exhaust).
ventilation system, indoor air quality
#NO 10042 Construction of a new bullet train car providing satisfactory
air to both smokers and non-smokers.
Ishii I, Sakurai T, et al
Indoor Air '96, proceedings of the 7th International Conference on Indoor
Air Quality and Climate, held July 21-26, 1996, Nagoya, Japan, Volume 2,
pp 151-156.
A new bullet train car with an effective ventilation system has been constructed
as a result of co-operation between Japan Tobacco In. and East Japan Railway
Company. The purpose of this system is to provide satisfactory and good quality
air both to smokers and non-smokers on board. The principal aim of the system
is to control the air stream in the carriage so as to prevent the tobacco
smoke in the smoking section from moving into the non-smoking section. Moreover,
an electrostatic precipitator and a deodorant filter were installed. The
efficiency of this system was examined using this new train car.
motor vehicle, tobacco smoke
#NO 10157 Indoor Air '96. Volume 4
Yoshizawa S, et al (eds.)
Japan, Proceedings of the 7th International Conference on Indoor Air Quality
and Climate, held July 21-26, 1996, Nagoya, Vol 4, 469pp.
Not for loan from AIVC Library.Contains sessions on: indoor air pollutants
- radon and ETS; indoor air pollutants - SPM; contamination control; physiology;
indoor air pollutants - odour; architectural design issues; workshops.
radon, tobacco smoke, odour, building design
#NO 10189 Two pronged investigation finds standard ventilation controls ETS.
Anon
USA, Indoor Air Quality Update, November 1996, pp 5-8.
Describes a study which measured six phase-selective ETS exposure markers,
using both fixed and personal monitors. The results were compared to determine
whether there was agreement between the two measuring methods and correlated
with building HVAC parameters to determine the effect ventilation systems
had on environmental tobacco smoke exposure.
tobacco smoke, ventilation strategy, pollutant
#NO 10190 Effectiveness of auxiliary air cleaners in reducing ETS components
in offices.
Pierce W M, Janczewski J N, Roethlisberger B, Pelton M, Kunstel K
USA, Ashrae Journal, November 1996, pp 51-57, 3 figs, 2 tabs, refs.
A field study was conducted to evaluate the effectiveness of several auxiliary
air cleaning devices in reducing components of environmental tobacco smoke
within a designated smoking lounge and ambient areas in an office suite.
Monitoring was performed for the ETS components nicotine, respirable particulate
and carbon monoxide. Results of the study indicated that auxiliary air cleaning
devices operating concurrently with dilution ventilation can be effective
in reducing the levels of nicotine and RSP in a designated smoking area.
They indicate that air cleaning devices equipped with HEPA filters are most
effective in reducing RSP levels. Devices equipped with carbon media are
most effective in reducing levels of nicotine. Results of the study also
indicate that physical separation when combined with dilution ventilation
is effective in controlling the migration of ETS components from a smoking
lounge to nonsmoking areas. In addition to the filtration technology used
in the device, there are a number of other factors that should be considered
when controlling the levels of ETS in a smoking lounge, including: the amount
of outside air supplied to the lounge; the flow rate of the device; the size
of the smoking lounge; the number of cigarettes being smoked; and the pressure
differences between the smoking area and the surrounding areas. It should
also be noted that there are other filtration technologies that can control
ETS, including electrostatic precipitation, not mentioned in the study.
air cleaning, tobacco smoke, passive smoking
#NO 10420 The effectiveness of designated smoking areas in controlling non-smokers
exposure to environmental tobacco smoke.
Sterling E, Collett C, Ross J
Indoor and Built Environment, No 6, 1997, pp 29-44, 9 tabs, 26 refs.
Field monitoring was conducted in office buildings in Seattle and Dallas
to assess the effectiveness of various workplace smoking configurations in
controlling non-smokers exposure to environmental tobacco smoke (ETS). Simultaneous
measurements of vapour-phase and particle-phase tracers of ETS were conducted
in adjacent smoking and non-smoking areas. Pressure relationships between
smoking and non-smoking areas were determined. The Seattle portion of the
study focused on the directin filtration of ETS from smoking to non-smoking
areas, as minimalre circulation of return air was occurring. Negative pressurisation
of smoking areas eliminated the direct migration of ETS. Tracers of ETS exposure
were not detected in non-smoking areas adjacent to negatively pressurized
smoking lounges. In the Dallas study buildings, the impact of recirculation
of ETS through the heating, ventilation and air-conditioning systems was
assessed. Vapour-phase ETS constituents were recirculated into non-smoking
areas at diluted concentrations. However, elevated particle-phase constituents
were not found in non-smoking areas. The overall results indicate that non-smokers
exposure to ETS can be effectively reduced in the office workplace without
regulations or policies that require either direct exhaust of air from smoking
areas to the outdoors by dedicated ventilation systems or total prohibition
of smoking within buildings.
tobacco smoke, pollutant, field monitoring
#NO 10712 Casino investigation finds ETS exposure among workers.
Anon
USA, IEQ Strategies, May 1997, pp 4-6, 1 tab.
An IEQ investigation at a UK casino found elevated blood and urine cotinine
concentrations among nonsmoking workers, although concentrations of airborne
contaminants were consistent with those found in other nonindustrial environments.
The investigators recommended nevertheless that smoking at the facility be
eliminated or more tightly controlled.
tobacco smoke
#NO 10757 Naturally ventilating UK non-domestic buildings: current
status and future policy.
Perera M D A E S, Shaw M R, Treadaway K
In: "A breath of fresh air: a new look at ventilation standards." Workshop,
UK, Building Research Establishment, March 1996.
Shows that there is considerable scope for making UK buildings tighter and
indicates the level of benefits that will accrue. UK activity in this area
is identified, including proposed statutory control in the form of revised
Building Regulations which will address issues of tightness for the first
time. Information is available on ventilation requirements necessary to satisfy
safety and health criteria. However, criteria relating to comfort, especially
those associated with odour, metabolic CO2, and summer overheating are still
being investigated. The paper sets out current thinking in this area, including
policies relating to minimising effects of tobacco smoking in public and
commercial buildings. The paper concludes by identifying currently available
UK design guidance on natural ventilation.
energy policy, natural ventilation, tobacco smoke
#NO 10944 Limitations of models for characterising indoor particle
concentrations from cigarette smoking in an office environment.
Bohanon H R, Cole K, Reynolds R J
Belgium, Proceedings of Clima 2000 Conference, held Brussels, August 30th
to September 2nd 1997, paper 331, 20pp, 8 tabs, 24 refs.
The first part of the paper uses results from tests that accurately measured
particle and gas concentrations during smoking in a real world office environment.
The test was conducted in a 511 square meter office space with ventilation
and smoking controlled and measured. The smoking rate was held constant throughout
the test under both integrated and segregated smoking conditions. Ventilation
or the office space was controlled to two rates; no mechanically delivered
outside air and full economizer. Part two explores a more detailed and controlled
test of particle concentration from cigarette smoking that was conducted
in a single office setting. This test measured and recorded activities on
a real time basis. The information gathered from this real time single office
observation is much more detailed than that from the large office space.
Evaluates single compartment models using the experimental data from the
large office space and from the more detailed single office.
particulate, tobacco smoke, modelling
#NO 11035 Control of occupant-generated indoor air sources in small
buildings through ventilation system retrofit.
Bayer C W, Fischer J
USA, Washington DC, Healthy Buildings/IAQ '97, 1997, proceedings of a conference
held Bethesda MD, USA, September 27 - October 2, 1997, Volume 2, pp 77-82,
4 figs, 6 refs.
A research study was undertaken investigating a retro-fit ventilation system
a strategic ventilation to provide a better indoor environment to smaller
buildings. A residential type HVAC unit interfaced with a desiccant energy
wheel was retro-fitted into the ventilation system of a small office space
built into a warehouse. The primary objective of this study was to minimize
environmental tobacco smoke transfer from smokers offices to nonsmokers offices
via the application of strategic ventilation.
ventilation system, retrofitting, occupant behaviour
#NO 11047 Decrease of occupational ETS in restaurants, development
of ventilation control technology.
Hyvarinen M J, Mielo T, Marttinen K, Reijula K, Welling I
USA, Washington DC, Healthy Buildings/IAQ '97, 1997, proceedings of a conference
held Bethesda MD, USA, September 27 - October 2, 1997, Volume 2, pp 433-438,
2 figs, 3 tabs, 4 refs.
Restaurant employees are exposed to high concentrations of environmental
tobacco smoke (ETS). The concentration of tobacco smoke in restaurants caries
in inverse proportion to the ventilation rate; ventilation rates are thus
important determinants of exposure to ETS. Field measurements of indoor air
quality and ventilation parameters were carried out in six Finnish restaurants.
The purpose of this study was to create design guidelines foe restaurant
ventilation systems. This study suggests that there is a threshold level
of air flow rate, approximately 40 dm3/s per person, beyond which there are
no significant improvements in air quality. This value cannot be considered
simply as a design goal; this would be too expensive in terms of energy consumption.
In some cases the air flow rate per person was very high and not contributing
significantly to indoor air quality (IAQ). This could be seen as justification
for demand controlled ventilation systems.
tobacco smoke, ventilation rate, field monitoring
#NO 11563 Building performance evaluation for indoor air quality using
occupant contaminant inhalation and attribution to contaminant sources.
Takemasa Y, Moser A
UK, Air Infiltration and Ventilation Centre, proceedings of "Ventilation
Technologies in Urban Areas", 19th Annual Conference, held Oslo, Norway,
28-30 September 1998, pp 293-304.
The emissions of building materials like volatile organic compounds and indoor
airborne contaminants such as environmental tobacco smoke expose occupants
to hazardous substances. Although impacts of indoor air quality problems
on human health, comfort, and productivity are quite large, no adequate evaluation
methodology exists to assess contaminant source control techniques and building
equipment systems. Even if instant indoor concentrations of many contaminants
are not always high, continuous exposures to these contaminants may cause
severe problems such as manifested by the sick building syndrome.
This paper proposes a method for evaluating long-term building performance
in terms of indoor air quality. The approach applies exposure assessment
but focuses on building performance. It employs the concept of using
the total amount of substance inhaled by persons who occupy the room.
This indicator is expressed by kilograms of each contaminant inhaled
by persons ever present in the building during its operational life.
The values include the effects of occupant rates. Concrete procedures
for deriving variations of the indicators for both gaseous and particulate
contaminants are described in detail. Another concept of contribution
rates of contaminant sources is introduced both for instant values
and on the inhalation basis. Evaluation examples of these indicators
for a simple office geometry are shown for particulate matter, carbon
dioxide, and formaldehyde. The results of the case studies strongly
suggest the importance of indoor material selection and ventilation
strategies. The contribution rate of contaminant sources makes it easier
to plan a remedy for bad indoor air quality. The applicability of these
indicators and future research requirements are also discussed.
occupant reaction, building performance
#NO 11873 Design for smoking areas: Part 1 - Fundamentals.
Nelson P R, Bohanon H R, Walker J C
USA, ASHRAE, 1998, in: the ASHRAE Transactions CD, proceedings of the 1998
ASHRAE Annual Meeting, held Toronto, Canada, June 1998, 12 pp, 4 figs, 4
tabs, refs.
ASHRAE currently provides little practical information for optimizing the
design of a cigar or s |